YORK INTERNATIONAL
NOTES:
1. For leaving brine temperature below 4.40°C (40°F), contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 12.8°C (55°F) contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freezing to -28.8°C (-20°F) with an electric heater as standard.
TEMPERATURE AND FLOWS
(SI UNITS)
Technical Data
Excessive flow, above the max l/s,
will damage the evaporator.
MODEL LEAVING WATER COOLER FLOW AIR ON
NUMBER TEMPERATURE (°C) (L/S)
3
CONDENSER (°C)
YCAS MIN.
1
MAX.
2
MIN. MAX. MIN. MAX
0283EC 4.4 12.8 7.0 38.0 -17.7 51.7
0303EC 4.4 12.8 8.0 38.0 -17.7 51.7
0323EC 4.4 12.8 8.0 38.0 -17.7 51.7
0343EC 4.4 12.8 8.0 38.0 -17.7 51.7