EasyManua.ls Logo

York R123 - Fig. 54 - Operation Sequence & Timing Diagram (Electro-Mechanical & Solid State Starter Applications); Fig. 55 - Operation Sequence & Timing Diagram (Compressor Motor Variable Speed Drive Applications)

York R123
156 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
YORK INTERNATIONAL
126
FORM 160.55-O1 (604)
"SYSTEM SHUTDOWN"
DISPLAY
MESSAGE
"SYSTEM RUN"
"SYSTEM PRELUBE"
(OIL PUMP PRE-RUN)
"SYSTEM COASTDOWN"
(OIL PUMP POST-RUN)
0 25 30 330 1800
(0.4) (0.5) (5.5) (30)
START
RESTART (IF
FIVE SUCCESSIVE
RESTARTS HAVE
NOT OCCURRED)
RESTART (ONLY
AFTER THE FIFTH
SUCCESSIVE RESTART)
TIME IN SECONDS (MINUTES)
ENERGIZE
(OPEN)
VENT 
SOLENOID
CHECK
OIL PRESS.
150 SEC.
(2.5 MIN.)
"SYSTEM SHUTDOWN"
DISPLAY
MESSAGE
"SYSTEM RUN"
"SYSTEM PRELUBE"
(OIL PUMP PRE-RUN)
"SYSTEM COASTDOWN"
(OIL PUMP POST-RUN)
0 25 30 330 1800
(0.4) (0.5) (5.5) (30)
START
TIME IN SECONDS (MINUTES)
ENERGIZE
(OPEN)
VENT LINE
SOLENOID
CHECK
OIL PRESS.
150 SEC.
(2.5 MIN.)
RESTART
FIG. 54 – OPERATION SEQUENCE TIMING DIAGRAM
(ELECTRO-MECHANICAL AND SOLID STATE STARTER APPLICATIONS)
LD04643
System Op er at ing Pro ce dures
FIG. 55 – OPERATION SEQUENCE TIMING DIAGRAM
(COMPRESSOR MOTOR VARIABLE SPEED DRIVE APPLICATIONS)
LD04644