036-21031-004 Rev. A (0603)
18 Unitary Products Group
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. E4FH024S06
EVAPORATOR COIL MODEL NO. F2RP/F2FP030
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
750 800 850
MBTUH K.W. C.O.P. MBTUH K.W. C.O.P. MBTUH K.W. C.O.P.
60
60 29.0 2.17 4.06 29.3 2.13 4.17 29.6 2.09 4.29
70 28.3 2.33 3.68 28.8 2.29 3.81 29.3 2.26 3.94
80 27.6 2.54 3.29 28.3 2.50 3.44 29.0 2.46 3.58
47
60 24.6 1.99 3.62 25.1 1.98 3.72 25.7 1.97 3.82
70 23.5 2.13 3.23 24.0 2.12 3.32 24.5 2.11 3.41
80 22.5 2.31 2.85 22.9 2.30 2.92 23.3 2.28 2.99
40
60 22.8 1.92 3.43 23.0 1.92 3.47 23.3 1.91 3.52
70 21.4 2.04 3.02 21.4 2.03 3.06 21.5 2.01 3.09
80 19.9 2.20 2.62 19.8 2.17 2.64 19.7 2.14 2.65
30
60 18.2 1.77 2.96 18.6 1.76 3.03 18.9 1.75 3.10
70 17.7 1.91 2.66 17.7 1.89 2.69 17.7 1.88 2.71
80 17.2 2.09 2.36 16.8 2.07 2.34 16.5 2.04 2.32
17
60 12.9 1.59 2.39 13.2 1.59 2.44 13.4 1.59 2.48
70 12.7 1.72 2.16 12.9 1.72 2.20 13.1 1.72 2.24
80 12.5 1.89 1.93 12.6 1.89 1.96 12.8 1.88 1.99
10
60 10.7 1.49 2.20 10.9 1.50 2.22 11.1 1.51 2.25
70 10.2 1.62 1.92 10.3 1.63 1.94 10.4 1.63 1.96
80 9.6 1.79 1.64 9.7 1.79 1.65 9.8 1.80 1.66
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
F2RP/F2FP024 1.00 1.00 1.00
G2FD035(S,H)14 1.00 1.02 0.98
G2FD030(S,H)17 1.00 1.02 0.98
G2FD024(S,H)14,17 0.99 0.97 1.02