Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
85
°
F95
°
F
To t al
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
To t a l
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F Entering Dry Bulb,
°
F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
5000
72 159 11.0 118 103 88 73 58 - - 151 11.8 115 100 85 70 55 - -
67 142 10.8 138 123 108 93 78 63 48 135 11.6 135 122 107 92 77 62 47
62 133 10.5 133 133 131 116 101 86 71 125 11.3 125 125 125 110 95 80 65
57 136 10.4 136 136 136 121 106 91 76 131 11.2 131 131 131 116 101 86 72
4500
72 153 11.0 109 96 82 69 56 - - 145 11.8 106 92 79 65 52 - -
67 138 10.8 129 116 103 89 76 62 49 131 11.6 126 114 101 87 74 60 47
62 128 10.4 128 128 123 109 96 82 69 120 11.2 120 120 119 106 93 79 66
57 131 10.4 131 131 128 115 101 88 74 126 11.2 126 126 123 110 97 83 70
4000
72 146 10.9 101 89 77 65 53 - - 140 11.7 96 85 73 61 49 - -
67 134 10.7 121 109 97 85 73 61 50 128 11.5 118 106 94 82 70 58 46
62 123 10.4 123 123 115 103 91 79 67 115 11.2 115 115 115 103 91 79 67
57 126 10.4 126 126 120 108 96 84 72 121 11.2 121 121 115 104 92 80 68
3500
72 144 10.9 94 83 72 62 51 - - 137 11.6 89 79 68 58 47 - -
67 131 10.7 112 101 90 80 69 59 48 124 11.4 108 98 87 77 66 55 45
62 121 10.3 121 117 108 97 87 76 66 113 11.1 113 112 107 97 86 76 65
57 124 10.3 124 120 113 102 92 81 71 119 11.1 119 116 108 98 87 77 66
3000
72 142 10.8 86 77 68 59 49 - - 135 11.5 82 73 64 54 45 - -
67 127 10.6 102 93 84 74 65 56 47 121 11.3 99 90 80 71 62 53 43
62 120 10.3 120 110 101 92 83 73 64 111 11.0 111 110 100 91 82 73 63
57 122 10.2 122 115 106 97 87 78 69 117 11.0 117 110 101 92 83 73 64
COOLING CAPACITIES
- 10 TON (BHN120)
Air On
Indoor
Coil
Temperature of Air on Outdoor Coil
105
°
F115
°
F
To t al
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
Tota l
Cap.
1
MBH
Power
Input
2
KW
Sensible Capacity
1
, MBH
CFM
WB
°
F
Entering Dry Bulb,
°
F Entering Dry Bulb,
°
F
86 83 80 77 74 71 68 86 83 80 77 74 71 68
5000
72 138 12.5 109 94 79 64 50 - - 124 13.2 104 89 74 59 44 - -
67 121 12.3 121 115 102 87 72 57 42 108 12.9 108 108 97 82 67 52 37
62 112 11.9 112 112 112 97 82 67 52 99 12.6 99 99 99 84 69 54 39
57 118 11.9 118 118 118 103 89 74 59 105 12.5 105 105 105 91 76 61 46
4500
72 132 12.5 101 87 74 60 47 - - 119 13.1 96 82 69 55 42 - -
67 118 12.2 115 108 96 82 69 56 42 104 12.9 104 102 91 78 64 51 37
62 107 11.9 107 107 106 93 80 66 53 94 12.5 94 94 93 80 67 53 40
57 114 11.8 114 114 111 98 84 71 57 101 12.4 101 101 99 85 72 58 45
4000
72 126 12.4 92 80 68 56 44 - - 113 13.1 87 75 63 51 39 - -
67 114 12.2 109 102 90 78 66 54 42 101 12.8 101 97 85 73 61 49 38
62 103 11.8 103 103 102 90 78 66 54 90 12.5 90 90 89 77 65 53 41
57 109 11.8 109 109 104 92 80 68 56 96 12.3 96 96 92 80 68 56 44
3500
7212412.38574635342 - - 11113.08069594838 - -
67 111 12.1 102 93 83 72 61 51 40 98 12.7 95 89 78 68 57 46 36
62 101 11.7 101 100 95 84 74 63 53 88 12.4 88 87 82 72 61 51 40
57 107 11.7 107 104 97 86 76 65 54 95 12.2 95 92 85 75 64 53 43
3000
72 122 12.2 77 68 59 50 40 - - 109 12.9 73 63 54 45 36 - -
6710812.0948576665748399512.690807162534334
62 99 11.6 99 97 88 79 70 60 51 87 12.3 87 85 76 67 57 48 39
57 105 11.6 105 99 90 81 71 62 53 93 12.1 93 88 79 69 60 51 42
1
These capacities are gross ratings. For net capacity, determine the KW of the supply air blower motor from the Blower Performance Table, multiply this value by 3.415 MBH / KW to determine the
motor heat, and deduct this heat from the gross capacity of the unit.
2
These ratings include the compressor and the outdoor fan motors but not the supply air blower motor.
ALL SENSIBLE CAPACITY
NOMINAL RATING
511.17-TG2Y
6 Unitary Products Group