Loading...
362242-YIM-B-0109
Johnson Controls Unitary Products 21
072
(6.0)
208-3-60 19.2 146.0 30.0 2.3 10.9 0.0
None - - - 37.2 50
E05 4.0 1 11.1 51.1 60
E07 5.6 1 15.5 56.6 70
E10 8.0 1 22.2 65.0 70
E15 11.9 2 33.0 78.5 80
E20 15.9 2 44.1 92.4 100
E30 22.2 2 61.6 114.2 125
230-3-60 19.2 146.0 30.0 2.3 10.9 0.0
None - - - 37.2 50
E05 5.3 1 13.3 53.1 60
E07 7.5 1 18.8 59.8 70
E10 10.6 1 26.6 69.1 80
E15 15.9 2 39.9 85.0 90
E20 21.2 2 53.2 100.9 110
E30 29.6 2 74.3 126.2 150
460-3-60 8.3 73.0 13.0 1.3 5.3 0.0
None - - - 17.0 25
E07 6.8 1 8.5 27.2 30
E10 10.1 1 12.7 32.2 35
E15 13.6 2 17.1 37.4 40
E20 19.5 2 24.5 46.3 50
E30 28.8 2 36.1 60.3 70
575-3-60 7.1 60.0 11.0 1.3 4.1 0.0
None - - - 14.0 20
E10 10.6 1 10.6 26.8 30
E15 15.9 1 16.0 33.1 35
E20 21.2 2 21.3 39.5 40
E30 30.4 2 30.5 50.6 60
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
TABLE 9: ELECTRICAL DATA - BP036-072 DIRECT DRIVE W/POWERED CONVENIENCE OUTLET
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps
036
(3.0)
208-1-60 11.5 68.0 17.5 2.3 6.0 10.0
None - - - 32.7 40
E05 4.0 1 19.2 56.7 60
E07 5.6 1 26.9 66.3 70
E10 8.0 1 38.5 80.8 90
E15 11.9 2 57.2 104.2 110
E20 15.9 2 76.4 128.2 150
230-1-60 11.5 68.0 17.5 2.3 6.0 10.0
None - - - 32.7 40
E05 5.3 1 23.0 60.3 70
E07 7.5 1 32.6 71.7 80
E10 10.6 1 46.1 87.9 90
E15 15.9 2 69.1 115.5 125
E20 21.2 2 92.2 143.1 150
208-3-60 8.3 68.0 13.0 2.3 6.0 10.0
None - - - 29.1 35
E05 4.0 1 11.1 43.0 50
E07 5.6 1 15.5 48.5 50
E10 8.0 1 22.2 56.9 60
E15 11.9 2 33.0 70.4 80
E20 15.9 2 44.1 84.3 90
230-3-60 8.3 68.0 13.0 2.3 6.0 10.0
None - - - 29.1 35
E05 5.3 1 13.3 45.0 50
E07 7.5 1 18.8 51.7 60
E10 10.6 1 26.6 61.0 70
E15 15.9 2 39.9 76.9 80
E20 21.2 2 53.2 92.8 100
TABLE 8: ELECTRICAL DATA - BP036-072 BELT DRIVE HIGH STATIC W/O POWERED CONVENIENCE
OUTLET (CONT.)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max
Fuse
2
/
Breaker
3
Size
(Amps)
RLA LRA MCC FLA FLA FLA Model kW Stages Amps