EasyManua.ls Logo

York Sunline 2000 - Supply Air Blower Performance (Bp048 Belt Drive) - Bottom Duct Application; Supply Air Blower Performance (Bp060 Belt Drive) - Side Duct Application; Supply Air Blower Performance (Bp060 Belt Drive) - Bottom Duct Application; Yim-B

York Sunline 2000
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
362242-YIM-B-0109
Johnson Controls Unitary Products 31
TABLE 19: SUPPLY AIR BLOWER PERFORMANCE (BP048 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1000 685 0.43 775 0.50 862 0.57 945 0.65 1025 0.73 1103 0.82 1177 0.91 1248 1.00 1317 1.10 1384 1.20
1200 714 0.46 805 0.53 892 0.60 975 0.68 1055 0.76 1132 0.85 1207 0.94 1278 1.04 1347 1.13 1414 1.23
1400 749 0.52 840 0.58 927 0.66 1010 0.74 1090 0.82 1167 0.91 1242 1.00 1313 1.09 1382 1.19 1449 1.29
1600 789 0.60 880 0.67 967 0.74 1050 0.82 1130 0.91 1207 0.99 1282 1.08 1353 1.18 1422 1.27 1489 1.37
1800 833 0.73 924 0.80 1011 0.87 1094 0.95 1174 1.03 1251 1.12 1326 1.21 1397 1.30 1466 1.40 1533 1.50
2000 881 0.89 971 0.96 1058 1.03 1142 1.11 1222 1.20 1299 1.28 1373 1.37 1445 1.47 1514 1.57 1580 1.66
FS
4
TABLE 20: SUPPLY AIR BLOWER PERFORMANCE (BP060 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1200 727 0.45 810 0.52 889 0.60 966 0.68 1040 0.76 1110 0.85 1179 0.95 1244 1.04 1308 1.14 1369 1.24
1400 759 0.51 842 0.58 922 0.65 998 0.73 1072 0.82 1143 0.91 1211 1.00 1276 1.10 1340 1.20 1401 1.30
1600 795 0.60 878 0.67 958 0.74 1035 0.82 1108 0.91 1179 1.00 1247 1.09 1313 1.19 1376 1.28 1438 1.39
1800 836 0.72 919 0.79 999 0.87 1075 0.95 1149 1.03 1220 1.12 1288 1.22 1353 1.31 1417 1.41 1478 1.51
2000 880 0.89 963 0.96 1042 1.04 1119 1.12 1193 1.20 1263 1.29 1331 1.39 1397 1.48 1460 1.58 1522 1.68
2200 926 1.10 1009 1.17 1089 1.25 1166 1.33 1239 1.41 1310 1.50 1378 1.60 1444 1.69 1507 1.79 1568 1.89
2400 976 1.35 1059 1.42 1138 1.50 1215 1.58 1289 1.66 1359 1.75 1428 1.85 1493 1.94 1557 2.04 1618 2.14
2600 1028 1.64 1111 1.71 1190 1.78 1267 1.87 1340 1.95 1411 2.04 1479 2.13 1545 2.23 1608 2.33 - -
TABLE 21: SUPPLY AIR BLOWER PERFORMANCE (BP060 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1200 714 0.46 805 0.53 892 0.60 975 0.68 1055 0.76 1132 0.85 1207 0.94 1278 1.04 1347 1.13 1414 1.23
1400 749 0.52 840 0.58 927 0.66 1010 0.74 1090 0.82 1167 0.91 1242 1.00 1313 1.09 1382 1.19 1449 1.29
1600 789 0.60 880 0.67 967 0.74 1050 0.82 1130 0.91 1207 0.99 1282 1.08 1353 1.18 1422 1.27 1489 1.37
1800 833 0.73 924 0.80 1011 0.87 1094 0.95 1174 1.03 1251 1.12 1326 1.21 1397 1.30 1466 1.40 1533 1.50
2000 881 0.89 971 0.96 1058 1.03 1142 1.11 1222 1.20 1299 1.28 1373 1.37 1445 1.47 1514 1.57 1580 1.66
2200 932 1.10 1022 1.17 1109 1.24 1193 1.32 1273 1.40 1350 1.49 1424 1.58 1496 1.67 1565 1.77 1631 1.87
2400 986 1.34 1076 1.41 1163 1.48 1246 1.56 1327 1.64 1404 1.73 1478 1.82 1550 1.92 1619 2.01 1685 2.11
2600 1042 1.62 1132 1.69 1219 1.76 1303 1.84 1383 1.92 1460 2.01 1534 2.10 1606 2.20 1675 2.29 - -