TABLE 12: ELECTRIC HEAT CORRECTION
FACTORS
NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER
208
208 0.75
240
230 0.92
480
460 0.92
600
575 0.92
TABLE 13: VOLTAGE LIMITATIONS
1
POWER SUPPLY
VOLTAGE
MIN. MAX.
208/230-1-60
187 253
208/230-3-60
187 253
460-3-60
414 506
575-3-60
518 630
1. Utilization Range “A” in accordance with ARI Standard
110.