362242-YIM-B-0109
30 Johnson Controls Unitary Products
TABLE 16: SUPPLY AIR BLOWER PERFORMANCE (BP036 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
800 633 0.37 734 0.41 828 0.47 914 0.54 994 0.61 1069 0.69 1139 0.77 1205 0.85 1268 0.94 1328 1.03
1000 656 0.41 757 0.46 851 0.52 937 0.58 1017 0.66 1092 0.73 1162 0.81 1228 0.90 1291 0.99 1351 1.08
1200 680 0.47 781 0.52 874 0.58 960 0.65 1041 0.72 1115 0.80 1185 0.88 1251 0.96 1314 1.05 1375 1.14
1400 706 0.56 807 0.61 901 0.67 987 0.73 1067 0.80 1142 0.88 1212 0.96 1278 1.05 1341 1.13 1401 1.22
1600 737 0.67 839 0.72 932 0.77 1018 0.84 1098 0.91 1173 0.99 1243 1.07 1309 1.15 1372 1.24 1433 1.33
FS
4
TABLE 17: SUPPLY AIR BLOWER PERFORMANCE (BP036 BELT DRIVE) - BOTTOM DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
4. Field Supplied Drive.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
800 612 0.38 722 0.43 824 0.48 918 0.55 1006 0.61 1087 0.69 1163 0.77 1235 0.85 1304 0.94 1370 1.02
1000 638 0.42 748 0.47 849 0.53 944 0.59 1031 0.66 1112 0.74 1188 0.82 1260 0.90 1329 0.98 1395 1.07
1200 663 0.48 773 0.53 875 0.59 969 0.65 1056 0.72 1138 0.80 1214 0.88 1286 0.96 1354 1.04 1420 1.13
1400 692 0.57 802 0.61 904 0.67 998 0.73 1085 0.80 1167 0.88 1243 0.96 1315 1.04 1383 1.13 1449 1.21
1600 726 0.67 836 0.72 938 0.78 1032 0.84 1119 0.91 1201 0.98 1277 1.06 1349 1.15 1417 1.23 1483 1.32
FS
4
TABLE 18: SUPPLY AIR BLOWER PERFORMANCE (BP048 BELT DRIVE) - SIDE DUCT APPLICATION
Air
Flow
(CFM)
Available External Static Pressure - IWG
1
1. Blower performance includes 1” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
Field Supplied Drive Standard Drive Option HIgh Static Drive Option
1000 699 0.42 782 0.49 862 0.56 939 0.64 1012 0.73 1083 0.82 1151 0.91 1217 1.01 1280 1.11 1341 1.21
1200 727 0.45 810 0.52 889 0.60 966 0.68 1040 0.76 1110 0.85 1179 0.95 1244 1.04 1308 1.14 1369 1.24
1400 759 0.51 842 0.58 922 0.65 998 0.73 1072 0.82 1143 0.91 1211 1.00 1276 1.10 1340 1.20 1401 1.30
1600 795 0.60 878 0.67 958 0.74 1035 0.82 1108 0.91 1179 1.00 1247 1.09 1313 1.19 1376 1.28 1438 1.39
1800 836 0.72 919 0.79 999 0.87 1075 0.95 1149 1.03 1220 1.12 1288 1.22 1353 1.31 1417 1.41 1478 1.51
2000 880 0.89 963 0.96 1042 1.04 1119 1.12 1193 1.20 1263 1.29 1331 1.39 1397 1.48 1460 1.58 1522 1.68