362242-YIM-B-0109
6 Johnson Controls Unitary Products
INSTALLATION
INSTALLATION SAFETY INFORMATION
Read these instructions before continuing this appli-
ance installation. This is an outdoor combination heat-
ing and cooling unit. The installer must assure that
these instructions are made available to the consumer
and with instructions to retain them for future reference.
1. Install this unit only in a location and position as
specified on page 7 of these instructions.
2. This equipment is not to be used for temporary
heating of buildings or structures under construc-
tion.
LIMITATIONS
These units must be installed in accordance with the
following national and local safety codes:
In U.S.A
.:
National Electrical Code ANSI/NFPA No. 70.
In Canada
:
Current Canadian Electrical Code C22.1.
Local plumbing and waste water codes.
Other applicable local codes.
Refer to the Unit Application Data Table 1 and the
Electrical Data table for the unit.
If components are to be added to a unit to meet local
codes, they are to be installed at the dealer's and/or
the customer's expense.
Size of unit for proposed installation should be based
on heat loss/heat gain calculation made according to
the methods of the Air Conditioning Contractors of
America (ACCA).
This unit is not to be used for temporary heating of
buildings or structures under construction.
The Simplicity® control board used in this
product will effectively operate the cooling
system down to 0°F when this product is
applied in a comfort cooling application for
people. An economizer is typically included in
this type of application. When applying this
product for process cooling applications
(computer rooms, switchgear, etc.), please
reference applications bulletin AE-011-07 or
call the applications department for Unitary
Products @ 1-877-UPG-SERV for guidance.
Additional accessories may be needed for
stable operation at temperatures below 30°
F.
TABLE 1: UNIT APPLICATION DATA (BP)
UNIT MODEL NUMBER 036 048 060 072
Voltage Variation,
Min. / Max.
1
1. Utilization range “A” in accordance with ARI Standard 110.
208/230 187/253
460 414/506
575 518/630
Supply Air CFM, Nom. 1200 1600 2000 2400
Wet Bulb Temperature (ºF) of Air on
Evaporator Coil, Min./Max
57/72
Dry Bulb Temperature (ºF) of Air on
Condenser Coil, Min./Max.
0/125