362242-YIM-B-0109
Johnson Controls Unitary Products 45
on the LED. If the compressor is locked out, cancel
any call for cooling. This will reset any compressor
lock outs.
NOTE: While the above step will reset any lockouts,
the compressor may be held off for the ASCD.
See the next step.
10. If 24 volts is present at the UCB Y1 terminal and
none of the switches are open and the compressor
is not locked out, the UCB may have the compres-
sor in an ASCD. Check the LED for an indication of
an ASCD cycle. The ASCD should time out within
5 minutes. Press and release the TEST button to
reset all ASCDs.
11. If 24 volts is present at the UCB Y1 terminal and the
compressor is not out due to a protective switch trip,
repeat trip lock out, or ASCD, the economizer termi-
nals of the UCB may be improperly wired. Check for
24 volts at the Y1 “OUT” terminal of the UCB. If 24
volts is present, trace the wiring from Y1 “OUT” for
incorrect wiring. If 24 volts is not present at the Y1
“OUT” terminal, the UCB must be replaced.
12. For units without economizers: If 24 volts is present
at the Y1 OUT terminal, check for 24 volts at the
Y1 “ECON” terminal. If 24 volts is not present,
check for loose wiring from the Y1 “OUT” terminal
to the Mate-N-Lock plug, the jumper in the Mate-N-
Lock plug, and in the wiring from the Mate-N-Lock
plug to the Y1 “ECON” terminal.
13. For units with economizers: If 24 volts is present at
the Y1 “OUT” terminal, check for 24 volts at the Y1
“ECON” terminal. If 24 volts is not present, check
for loose wiring from the Y1 “OUT” terminal to the
Mate-N-Lock plug, a poor connection between the
UCB and economizer Mate-N-Lock plugs, loose
wiring from the Mate-N-Lock plug to the econo-
mizer, back to the Mate-N-Lock plug, and from the
Mate-N-Lock plug to the Y1 “ECON” terminal. If
nothing is found, the economizer actuator may
have faulted and is failing to return the 24-volt “call”
to the Y1 “ECON” terminal even though the econo-
mizer is not providing free cooling. To test, discon-
nect the Mate-N-Locks and jumper between the
WHITE and YELLOW wires of the UCB’s Mate-N-
Lock plug. If the compressor energizes, there is a
fault in the economizer wiring or actuator.
14. The UCB can be programmed to lock out compres-
sor operation during free cooling and in low ambi-
ent conditions. These options are not enabled by
default. Local distributors can test the UCB for this
programming.
For units with factory installed economizers, the
UCB is programmed to lock out compressor opera-
tion when the LAS set point is reached.
For units without factory installed or with field
installed economizers, the UCB allows compressor
operation all the time. This programming can be
checked or changed by the local distributor.
15. If none of the above correct the error, replace the
UCB.