37
MODEL: YCIV0760E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25.0 30.0 35.0 40.0 45.0 46.0
(°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP
5.0
672.7 155.1 3.9 661.6 178.9 3.4 648.7 206.1 2.9 631.4 236.7 2.5 586.1 249.7 2.2 577.1 252.0 2.2
6.0
691.7 156.1 4.0 680.1 179.4 3.5 666.7 206.4 3.0 647.0 236.3 2.6 600.4 249.7 2.3 591.1 252.1 2.2
7.0
711.0 157.3 4.1 699.0 180.0 3.6 685.1 206.8 3.1 662.9 235.8 2.6 614.9 249.6 2.3 605.4 252.0 2.3
8.0
730.8 158.7 4.2 718.3 180.9 3.6 703.9 207.3 3.1 678.8 235.3 2.7 629.7 249.3 2.4 620.0 251.8 2.3
9.0
750.9 160.4 4.2 737.9 181.8 3.7 723.0 207.9 3.2 695.2 234.8 2.8 645.0 249.0 2.4 634.8 251.6 2.4
10.0
771.3 162.3 4.3 758.0 183.0 3.8 742.4 208.8 3.3 711.9 234.3 2.8 660.3 248.5 2.5 650.0 251.1 2.4
11.0
792.1 164.4 4.4 778.4 184.3 3.9 762.2 209.6 3.4 728.8 233.8 2.9 675.9 248.0 2.6 665.4 250.7 2.5
12.0
813.3 166.8 4.4 799.1 186.0 3.9 782.4 210.6 3.4 745.9 233.3 3.0 691.8 247.5 2.6 681.0 250.2 2.6
13.0
834.9 169.5 4.5 820.2 187.8 4.0 803.0 211.8 3.5 763.0 233.0 3.1 707.8 247.0 2.7 696.9 249.6 2.6
MODEL: YCIV0800E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25.0 30.0 35.0 40.0 45.0 46.0
(°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP
5.0
715.1 163.2 3.9 703.9 187.3 3.4 691.1 214.8 3.0 672.4 245.0 2.6 630.3 261.6 2.3 620.8 264.1 2.2
6.0
735.3 164.3 4.0 723.6 188.0 3.5 710.2 215.4 3.0 689.7 245.2 2.6 645.5 261.6 2.3 635.9 264.1 2.3
7.0
755.9 165.6 4.1 743.7 188.9 3.6 729.7 216.0 3.1 707.4 245.3 2.7 661.1 261.5 2.4 651.2 264.1 2.3
8.0
776.9 167.1 4.2 764.2 189.8 3.7 749.5 216.7 3.2 725.4 245.4 2.8 677.0 261.3 2.4 666.7 264.0 2.4
9.0
798.4 168.8 4.3 785.1 191.0 3.8 769.8 217.5 3.3 743.7 245.5 2.8 693.1 261.0 2.5 682.6 263.7 2.4
10.0
820.2 170.7 4.3 806.4 192.3 3.8 790.5 218.4 3.3 762.5 245.6 2.9 709.5 260.7 2.5 698.7 263.4 2.5
11.0
842.4 172.9 4.4 828.1 193.8 3.9 811.6 219.5 3.4 781.3 245.8 3.0 726.1 260.3 2.6 715.2 263.0 2.5
12.0
864.5 175.1 4.5 850.1 195.4 4.0 833.1 220.7 3.5 799.5 245.5 3.0 743.1 259.9 2.7 723.9 257.8 2.6
13.0
887.0 177.7 4.5 872.1 197.2 4.0 854.8 222.1 3.6 818.1 245.3 3.1 760.3 259.5 2.7 730.1 251.0 2.7
MODEL: YCIV0830E/V
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT 25.0 30.0 35.0 40.0 45.0 46.0
(°C) KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP KWi KWi COP
5.0
743.0 169.0 3.9 731.8 192.7 3.4 718.8 219.4 3.0 703.0 250.7 2.6 661.8 268.9 2.3 652.0 271.4 2.2
6.0
764.0 170.2 4.0 752.3 193.7 3.5 738.8 220.3 3.1 722.2 251.7 2.7 678.0 268.9 2.3 667.8 271.6 2.3
7.0
785.4 171.7 4.1 773.3 194.8 3.6 759.2 221.2 3.2 741.8 252.8 2.7 694.3 269.0 2.4 684.1 271.6 2.3
8.0
807.2 173.1 4.2 794.7 196.0 3.7 780.0 222.3 3.2 761.9 253.8 2.8 711.1 269.0 2.5 700.6 271.6 2.4
9.0
829.4 174.8 4.3 816.5 197.2 3.8 801.2 223.4 3.3 782.3 254.8 2.9 728.2 268.9 2.5 717.3 271.6 2.5
10.0
851.7 176.5 4.3 838.7 198.7 3.8 822.9 224.6 3.4 801.1 254.8 2.9 745.6 268.9 2.6 734.4 271.5 2.5
11.0
874.2 178.4 4.4 860.8 200.2 3.9 844.9 225.8 3.4 820.0 254.9 3.0 763.3 268.8 2.6 751.8 271.4 2.6
12.0
897.1 180.5 4.5 883.2 201.8 4.0 866.8 227.3 3.5 839.3 254.9 3.1 781.0 268.7 2.7 769.5 271.3 2.6
13.0
920.3 182.6 4.5 906.1 203.6 4.1 889.1 228.7 3.6 858.7 255.0 3.1 799.3 268.6 2.8 787.3 271.3 2.7
NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kW
i
= Compressor kW Input
3. COP = Coefcient of Performance (includes condenser fan power)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based on 0.168 l/s cooler water per ton, and 0.018 (m
2
– °C)/kW
6. ARI 550/590 does not provide certication for 50Hz ratings. The unique use of the YCIV variable speed drive allows compressor operation at the output speed regardless of the input
power frequency. This allows for common unit/heat exchanger congurations between 60Hz and 50Hz with closely matching capacity.