JOHNSON CONTROLS
35
FORM 150.62-EG1 (507)
NOTES:
1. kWo = Unit kW Cooling Capacity Output
2. kWi = Compressor kW Input
3. COP = Coefcient of Performance (Based upon compressor and fan input kW)
4. LCWT = Leaving Chilled Water Temperature
5. Ratings based upon 0.15L/s cooler water per kW
COP=4.17
YCAL0074EB
COP=4.22
YCAL0080EB
YCAL0090EB
YCAL0094EB
COP=3.98
COP=3.92
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
265.6 72.1 3.4 252.2 80.2 2.9 238.3 89.2 2.5 224.1 99.1 2.1 176.4 85.8 1.9 138.2 74.4 1.7
6.0
274.4 72.7 3.5 260.6 80.9 3.0 246.3 89.9 2.6 231.7 99.8 2.2 182.7 86.3 2.0 143.3 74.8 1.8
7.0
283.4 73.3 3.5 269.2 81.5 3.1 254.5 90.6 2.6 239.5 100.5 2.2 189.1 86.8 2.0 148.4 75.2 1.8
8.0
292.6 73.9 3.6 278.0 82.1 3.1 262.9 91.3 2.7 247.4 101.3 2.3 195.7 87.4 2.1 153.3 76.0 1.9
9.0
301.9 74.5 3.7 286.9 82.8 3.2 271.4 92.0 2.8 255.5 102.1 2.4 202.3 87.9 2.1 158.8 76.3 1.9
10.0
311.5 75.2 3.8 296.0 83.5 3.3 280.1 92.7 2.8 263.8 102.9 2.4 175.8 69.3 2.3 164.3 76.8 2.0
11.0
321.2 75.9 3.9 305.3 84.2 3.4 288.9 93.5 2.9 272.3 103.7 2.5 181.8 69.7 2.4 170.0 77.2 2.0
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
289.2 79.7 3.3 274.8 88.8 2.9 260.0 98.7 2.5 244.7 109.6 2.1 162.1 74.0 2.0 151.1 82.1 1.7
6.0
298.5 80.5 3.4 283.8 89.5 3.0 268.5 99.4 2.5 252.8 110.4 2.2 167.8 74.3 2.1 156.5 82.5 1.8
7.0
308.2 81.2 3.5 293.0 90.2 3.0 277.3 100.3 2.6 261.1 111.3 2.2 173.7 74.8 2.1 162.0 83.0 1.8
8.0
317.9 81.9 3.6 302.4 91.0 3.1 286.2 101.1 2.7 269.5 112.2 2.3 179.7 75.2 2.2 167.7 83.4 1.9
9.0
328.0 82.6 3.7 312.0 91.7 3.2 295.3 101.9 2.7 278.1 113.2 2.3 185.8 75.6 2.3 173.4 83.9 1.9
10.0
338.2 83.3 3.8 321.7 92.5 3.2 304.6 102.8 2.8 286.9 114.1 2.4 192.1 76.1 2.3 179.3 84.4 2.0
11.0
348.6 84.1 3.8 331.5 93.5 3.3 314.0 103.7 2.8 295.9 115.1 2.4 198.5 76.5 2.4 185.4 84.9 2.0
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
292.8 74.6 3.4 278.8 82.1 3.0 264.1 90.5 2.6 248.3 100.2 2.2 232.8 110.2 1.9 212.8 124.3 1.6
6.0
303.1 75.2 3.5 288.7 82.7 3.1 273.6 91.1 2.7 257.3 100.7 2.3 241.3 110.9 2.0 221.0 124.7 1.6
7.0
313.6 75.7 3.6 298.8 83.3 3.2 283.2 91.7 2.8 266.6 101.3 2.4 250.0 111.5 2.0 229.4 125.1 1.7
8.0
324.3 76.3 3.7 309.1 83.9 3.3 293.1 92.4 2.8 276.0 102.0 2.5 257.7 113.0 2.1 238.0 125.6 1.7
9.0
335.2 76.9 3.8 319.6 84.6 3.4 303.1 93.1 2.9 285.6 102.6 2.5 266.9 113.6 2.2 246.8 126.2 1.8
10.0
346.2 77.7 3.9 330.3 85.3 3.4 313.4 93.8 3.0 295.4 103.3 2.6 276.2 114.3 2.2 255.6 126.8 1.9
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25°C 30°C 35°C 40°C 45°C 50°C
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
314.9 82.1 3.4 300.3 90.2 3.0 285.2 99.0 2.6 269.1 109.0 2.3 251.7 120.3 1.9 232.8 133.1 1.6
6.0
325.7 82.8 3.5 310.7 90.9 3.1 295.1 99.8 2.7 278.6 109.8 2.3 260.7 121.0 2.0 241.4 133.8 1.7
7.0
336.8 83.5 3.6 321.3 91.7 3.1 305.2 100.6 2.7 288.2 110.6 2.4 269.9 121.8 2.0 250.1 134.6 1.7
8.0
348.1 84.2 3.7 332.1 92.4 3.2 315.5 101.4 2.8 298.0 111.4 2.4 279.2 122.7 2.1 259.0 135.3 1.8
9.0
359.6 84.9 3.8 343.1 93.2 3.3 326.0 102.3 2.9 308.0 112.3 2.5 288.8 123.5 2.2 268.1 136.1 1.8
10.0
371.1 85.7 3.9 354.4 94.0 3.4 336.8 103.2 3.0 318.3 113.2 2.6 298.5 124.4 2.2 277.3 137.1 1.9
11.0
383.1 86.4 3.9 365.9 94.8 3.5 347.8 104.0 3.0 328.7 114.1 2.6 308.4 125.4 2.3 286.9 137.9 1.9