JOHNSON CONTROLS
36
YCAL0104EB
COP=4.10
YCAL0114EB
COP=4.06
YCAL0124EB
COP=3.91
Ratings - R-407C (SI Units)
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
351.9 94.2 3.4 334.3 103.9 2.9 315.5 115.0 2.5 295.4 127.9 2.1 273.6 142.9 1.8 213.4 122.9 1.6
6.0
363.8 95.1 3.4 345.6 104.9 3.0 326.3 116.0 2.6 305.6 128.9 2.2 283.3 143.9 1.8 221.4 123.5 1.7
7.0
375.9 96.0 3.5 357.2 105.9 3.1 337.4 117.0 2.6 316.1 130.0 2.2 293.2 144.9 1.9 229.6 124.2 1.7
8.0
388.3 97.0 3.6 369.1 106.9 3.1 348.6 118.2 2.7 326.8 131.0 2.3 303.5 145.9 1.9 237.9 124.9 1.8
9.0
401.0 98.0 3.7 381.1 108.0 3.2 360.1 119.3 2.8 337.8 132.1 2.4 313.9 147.0 2.0 246.4 125.6 1.8
10.0
413.9 99.0 3.8 393.5 109.1 3.3 371.9 120.4 2.8 349.0 133.3 2.4 324.6 148.1 2.0 255.1 126.4 1.9
11.0
427.0 100.1 3.9 406.1 110.2 3.4 384.0 121.5 2.9 360.5 134.4 2.5 335.5 149.2 2.1 198.9 88.4 2.0
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
394.9 102.1 3.4 375°F
112.8 3.0 353.7 125.1 2.5 330.6 139.7 2.2 305.8 157.0 1.8 278.8 177.7 1.5
6.0
408.5 103.0 3.5 388.1 113.7 3.0 366.2 126.1 2.6 342.6 140.6 2.2 317.0 157.9 1.8 289.5 178.3 1.5
7.0
422.4 103.9 3.6 401.4 114.7 3.1 378.9 127.1 2.7 354.7 141.5 2.3 328.5 158.7 1.9 300.4 179.0 1.6
8.0
436.5 104.9 3.7 415.0 115.7 3.2 392.0 128.1 2.8 367.1 142.5 2.3 340.3 159.6 2.0 311.6 179.8 1.6
9.0
450.9 106.0 3.8 428.9 116.8 3.3 405.2 129.2 2.8 379.7 143.6 2.4 352.4 160.6 2.0 323.1 180.6 1.7
10.0
465.6 107.1 3.8 443.0 117.9 3.4 418.7 130.3 2.9 392.7 144.7 2.5 364.7 161.6 2.1 334.9 181.4 1.7
11.0
480.7 108.2 3.9 457.5 119.1 3.4 432.6 131.4 3.0 405.9 145.8 2.5 377.4 162.6 2.1 347.0 182.3 1.8
AIR TEMPERATURE ON - CONDENSER (°C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP kWo kWi COP
5.0
425.1 114.2 3.3 404.5 125.8 2.9 382.5 139.0 2.5 358.9 154.1 2.1 333.4 171.7 1.8 258.3 152.3 1.6
6.0
439.5 115.3 3.4 418.3 127.0 3.0 395.7 140.1 2.6 371.5 155.2 2.2 345.3 172.8 1.8 268.1 152.9 1.6
7.0
454.2 116.4 3.5 432.3 128.1 3.0 409.2 141.4 2.6 384.3 156.4 2.3 357.5 173.9 1.9 278.0 153.7 1.7
8.0
469.2 117.6 3.6 446.7 129.4 3.1 422.9 142.6 2.7 397.2 157.7 2.3 369.9 175.1 2.0 288.2 154.4 1.7
9.0
484.5 118.7 3.6 461.4 130.6 3.2 436.8 143.9 2.8 410.7 159.0 2.4 382.6 176.3 2.0 298.6 155.2 1.8
10.0
500.2 119.9 3.7 476.3 131.9 3.3 451.2 145.1 2.8 424.4 160.3 2.4 395.6 177.6 2.1 309.2 156.1 1.8
11.0
516.1 121.1 3.8 491.7 133.1 3.3 465.8 146.5 2.9 438.4 161.6 2.5 408.9 178.9 2.1 320.1 156.9 1.9
YCAL0134EB
COP = 3.84
AIR TEMPERATURE ON ‑ CONDENSER (C)
LCWT
(°C)
25.0 30.0 35.0 40.0 45.0 50.0
KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP KWo KWi COP
5.0 455.4 126.4 3.2 434.0 138.9 2.8 411.5 152.8 2.5 387.3 168.5 2.1 361.1 186.4 1.8 237.9 126.8 1.7
6.0 470.5 127.7 3.3 448.5 140.3 2.9 425.3 154.2 2.5 400.5 169.9 2.2 373.6 187.8 1.9 246.7 127.6 1.7
7.0 486.0 128.9 3.4 463.3 141.6 3.0 439.4 155.7 2.6 413.9 171.4 2.2 386.4 189.1 1.9 255.7 128.3 1.8
8.0 501.9 130.2 3.5 478.4 143.0 3.0 453.8 157.1 2.7 427.5 173.0 2.3 399.5 190.6 2.0 264.8 129.1 1.9
9.0 518.1 131.4 3.6 493.9 144.4 3.1 468.5 158.6 2.7 441.7 174.3 2.3 412.9 192.0 2.0 274.1 129.9 1.9
10.0 534.8 132.7 3.6 509.7 145.8 3.2 483.7 160.0 2.8 456.1 175.8 2.4 426.6 193.5 2.1 283.6 130.7 2.0
11.0 551.6 134.0 3.7 526.0 147.2 3.3 499.2 161.5 2.8 470.8 177.4 2.5 440.5 195.1 2.1 293.3 131.5 2.0