YORK INTERNATIONAL
30
(YCHA100)
LWT COOLING RANGES
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.0°F Setpoint plus 0.5°F
SWITCH = 0 Loader Stage 3 Setpoint plus 0.5°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 0.5°F
OF
+ 1.0°F Compressor Stage 1 Setpoint minus 0.5°F Setpoint minus 1.0°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.2°F Setpoint plus 0.6°F
SWITCH = 1 Loader Stage 3 Setpoint plus 0.6°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 0.6°F
OF
+ 1.2°F Compressor Stage 1 Setpoint minus 0.6°F Setpoint minus 1.2°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.4°F Setpoint plus 0.7°F
SWITCH = 2 Loader Stage 3 Setpoint plus 0.7°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 0.7°F
OF
+ 1.4°F Compressor Stage 1 Setpoint minus 0.7°F Setpoint minus 1.4°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.5°F Setpoint plus 0.8°F
SWITCH = 3 Loader Stage 3 Setpoint plus 0.7°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 0.8°F
OF
+ 1.5°F Compressor Stage 1 Setpoint minus 0.7°F Setpoint minus 1.5°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.6°F Setpoint plus 0.8°F
SWITCH = 4 Loader Stage 3 Setpoint plus 0.8°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 0.8°F
OF
+ 1.6°F Compressor Stage 1 Setpoint minus 0.8°F Setpoint minus 1.6°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.8°F Setpoint plus 0.9°F
SWITCH = 5 Loader Stage 3 Setpoint plus 0.9°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 0.9°F
OF
+ 1.8° F Compressor Stage 1 Setpoint minus 0.9°F Setpoint minus 1.8°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 1.9°F Setpoint plus 1.1°F
SWITCH = 6 Loader Stage 3 Setpoint plus 1.1°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 1.1°F
OF
+ 1.9°F Compressor Stage 1 Setpoint minus 1.0°F Setpoint minus 1.9°F
STAGE ON OFF
COOLING RANGE Loader Stage 4 Setpoint plus 2.0°F Setpoint plus 1.0°F
SWITCH = 7 Loader Stage 3 Setpoint plus 1.0°F Setpoint
COOLING RANGE Loader Stage 2 Setpoint Setpoint minus 1.0°F
OF
+ 2.0°F Compressor Stage 1 Setpoint minus 1.0°F Setpoint minus 2.0°F