MICRO LOGIC BOARD JUMPERS/SWITCHES
The Micro Logic Board can be configured for various
options (Remote/Local Control and RWT/LWT Control).
These options are available on REV. B and REV. C Mi-
cro Logic Boards.
REV. B boards actually utilize three jumpers for these
options (J8, J9, and J10). REV. C boards replace the
jumpers with a Dip Switch which has 7 miniature rocker
switches built into a single pack. 2 of the 7 switches are
active.
An explanation of the Jumpers/Switches on the Micro
Logic Board is provided on this page and page 32.
(YCHA100)
MICRO LOGIC BOARD JUMPER OPTIONS (REV. B
BOARDS)
Three jumpers are available for the options on the Rev.
B Micro Logic Board.
J8: Spare
J9: Remote Temperature Setpoint Reset
OUT: Local (Panel Control Only)
IN: Remote (Remote Control of Temperature
Setpoint Reset. You must have a Digital
Input Board to use Remote Control.)
J10: Selects RWT or LWT Control
OUT: RWT Control
IN: LWT Control
See Figure below for J8, J9, and J10 location.
00008TG
FIG. 11 MICRO LOGIC BOARD JUMPERS (REV. “B” BOARD)
J8
J10
J9