EasyManua.ls Logo

York YD Series - Page 127

York YD Series
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
127
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
shutdown is performed. This check is only performed
under the following conditions:
• Chiller has been running for at least 10 minutes.
• Evaporator Refrigerant temperature (RT7) has
been enabled by a Service technician using in-
structions in YORK Service Manual 160.69.M1.
• Not in Brine cooling mode.
• Smart Freeze is enabled.
• Evaporator Temperature Sensor (RT7) or Evapo-
rator Saturation Temperature is indicating a tem-
perature of <32.0°F.
The chiller can be started after the temperatures are
within 3.0°F of one another and the COMPRESSOR
switch is placed in the Stop-reset (O) position.
“DISCHARGE #1 – HIGH PRESSURE CON-
TACTS OPEN”
The contacts of the electro-mechanical high pressure
switch (HP1, located in the discharge line of compres-
sor #1) have opened because it detected a pressure
>180.0 PSIG. The contacts will automatically close
when the discharge pressure decreases to < 120.0 PSIG
and
the COMPRESSOR Switch is placed in the Stop-reset
(O) position.
“DISCHARGE #2 – HIGH PRESSURE CON-
TACTS OPEN”
The contacts of the electro-mechanical high pressure
switch (HP2, located in the discharge line of compres-
sor #2) have opened because it detected a pressure
>180.0 PSIG. The contacts will automatically close
when the discharge pressure decreases to < 120.0 PSIG
and the
COMPRESSOR Switch is placed in the Stop-reset (O)
position.
“DISCHARGE #1 – HIGH TEMPERATURE”
The chiller (both compressors) has shutdown because
the discharge temperature of compressor #1, as sensed
by thermistor RT2, has increased to >220.0 ºF. The
chiller can be started after the temperature decreases to
<220.0 ºF and the COMPRESSOR switch is placed in
the Stop-reset (O) position.
With software version C.OPT.11.03.01.004 (or later),
if compressor #1 is locked-out using the Lockout key
on the Capacity Compressor Cycling Screen, this fault
does not cause compressor #2 to shutdown or prevent
it from starting. When this fault occurs on a locked-out
compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out
compressor. The condition must be corrected prior to
the lockout being removed from the compressor. If it
is not, the warning condition will revert back to a shut-
down as soon as the lockout is removed and will cause
the chiller to trip.
“DISCHARGE #2 – HIGH TEMPERATURE”
The chiller (both compressors) has shutdown because
the discharge temperature of compressor #2, as sensed
by thermistor RT8, has increased to >220.0 ºF. The
chiller can be started after the temperature decreases to
<220.0 ºF and the COMPRESSOR switch is placed in
the Stop-reset (O) position.
With software version C.OPT.11.03.01.004 (or later),
if compressor #2 is locked-out using the Lockout key
on the Capacity Compressor Cycling Screen, this fault
does not cause compressor #1 to shutdown or prevent
it from starting. When this fault occurs on a locked-out
compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out
compressor. The condition must be corrected prior to
the lockout being removed from the compressor. If it
is not, the warning condition will revert back to a shut-
down as soon as the lockout is removed and will cause
the chiller to trip.
“DISCHARGE #1 – LOW TEMPERATURE”
The chiller (both compressors) has shutdown because
the discharge temperature of compressor #1, as sensed
by thermistor RT2, has decreased to <30.0 ºF. The
chiller can be started after the temperature increases
to >30.0ºF and the COMPRESSOR switch is placed in
the Stop-reset (O) position.
With software version C.OPT.11.03.01.004 (or later),
if compressor #1 is locked-out using the Lockout key
on the Capacity Compressor Cycling Screen, this fault
does not cause compressor #2 to shutdown or prevent
it from starting. When this fault occurs on a locked-out
compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out
compressor. The condition must be corrected prior to
the lockout being removed from the compressor. If it
is not, the warning condition will revert back to a shut-
down as soon as the lockout is removed and will cause
the chiller to trip.

Table of Contents

Related product manuals