EasyManuals Logo

York YD Series User Manual

York YD Series
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #9 background imageLoading...
Page #9 background image
JOHNSON CONTROLS
9
FORM 160.69-O1
ISSUE DATE: 9/30/2012
1
Each compressor also has a Discharge Temperature
thermistor and High Pressure safety device.
There are two Liquid Line Solenoid Valves and two
Oil Return Solenoid Valves, one for each compressor.
A lockout can be performed on a compressor to pre-
vent it from running. Only one compressor at a time
can be locked out.
Two CM-2 Current Boards, one for each compressor
motor, provides motor Overload and Power Fault pro-
tection.
The Oil System consists of a common Oil Sump for
both compressors. A single Oil Heater maintains prop-
er Sump temperature when both compressors are shut-
down. This temperature is monitored by the Oil Tem-
perature Thermistor. There are two Oil pumps, one for
each compressor. Each is driven by a Variable Speed
Oil Pump Drive. The oil pressure is monitored by a
common Sump oil pressure transducer monitoring the
low side pressure. Two Pump oil pressure transduc-
ers, one for each compressor, monitor the high side oil
pressure for each compressor.
SECTION 1 – DESCRIPTION OF SYSTEM
AND FUNDAMENTALS OF OPERATION
SYSTEM OPERATION DESCRIPTION
The following is a high level description of the chill-
er control. It describes the overall operation. Control
Center components, chiller components and program-
mable setpoints are referenced. Refer to Figure 2 on
page 15 to view the chiller operation flowchart.
The YD dual compressor chiller consists of one evapo-
rator, one condenser, two oil pumps and two compres-
sors. Other than capacity control, the basic operation is
similar to a standard YK Centrifugal Chiller.
The use of two compressors requires valves on the dis-
charge line of each compressor. When a compressor
is shutdown, its discharge valve is closed to prevent
compressor backspin due to a gas flow from the run-
ning compressor. An end switch at both the closed and
open positions provides indication of full open and
full closed positions. The valves can be manually con-
trolled.
Each compressor Pre-rotation Vane assembly is
equipped with a potentiometer to provide vane posi-
tion. A calibration procedure assures displayed posi-
tion accuracy. The vanes can be manually controlled.
FIGURE 1 - MODEL YD CHILLER
COMPRESSOR 1
COMPRESSOR 2
MOTOR 1
MOTOR 2
CONTROL
CENTER
EVAPORATOR
CONDENSER
LD08634

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York YD Series and is the answer not in the manual?

York YD Series Specifications

General IconGeneral
BrandYork
ModelYD Series
CategoryChiller
LanguageEnglish

Related product manuals