EasyManua.ls Logo

York YD Series - Page 99

York YD Series
150 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
JOHNSON CONTROLS
99
SECTION 2 – OPTIVIEW CONTROL CENTER
FORM 160.69-O1
ISSUE DATE: 9/30/2012
2
second number. Although blank by default, the appro-
priate label and number can be entered by a Service
Technician. Service Technicians refer to Service Man-
ual 160.69-M1.
Chiller Style/Compressor
(Software version C.OPT.11.03.01.004(and later))
Access Level Required: SERVICE
Used to enter the chiller style/compressor combina-
tion. Once the chiller style/compressor combination
is entered, the program controls the chiller per the re-
quirements of the entered chiller and compressor. The
selection determines the minimum (default) allowable
coastdown duration programmable with the COAST-
DOWN TIME Setpoint on the SETUP Screen. Service
Technicians refer to YORK Service Manual 160.69-
M1.
Flow Switch (Digital/Analog)
Access Level Required: SERVICE
Configures the program to read the appropriate in-
put for the chilled and condenser water flow sensors.
The chiller will accept either site-installed paddle type
(Digital) flow sensors or factory mounted (Analog)
flow sensors to sense the evaporator and condenser wa-
ter flow. The paddle type flow sensors are identified
as Digital because they are equipped with normally
open contacts that, when closed, apply 115Vac to I/O
Board digital inputs on terminal TB4-12(evaporator)
and TB4-11(condenser). The factory mounted type
flow sensors are identified as Analog because they
are equipped with normally open contacts that, when
closed, apply +5vdc to the Microboard analog inputs
at J7-14(evaporator) and J7-16 (condenser). Service
Technicians refer to YORK Service Manual 160.69-
M1.
VGD (Enabled/Disabled)
(Software version C.MLM.11.02.xxx (and later) or
C.OPT.11.02.300 (and later))
Access Level Required: SERVICE
Enables and disables the Variable Geometry Diffuser
feature. If equipped with this feature, it should be en-
abled. Otherwise, it should be disabled.