SECTION 2 – PRODUCT DESCRIPTION
LOUVERED PANELS (CONDENSER COIL
ONLY)
Louvered panels are mounted on the sides and ends
of the condenser coils for protection. (Factory-
mounted)
LOUVERED PANELS (FULL UNIT)
Louvered panels surround the front, back, and
sides of the unit. They prevent unauthorized access
and visually screen unit components. Unrestricted
air ow is permitted through generously sized
louvered openings. This option is applicable for
any outdoor design ambient temperature up to 46°
(115°F). (Factory-mounted)
COIL END HAIL GUARD
Louvered panel attached to exposed coil end.
(Factory-mounted)
SOUND ATTENUATION
One or both of the following sound attenuation options
are recommended for residential or other similar sound
sensitive locations:
COMPRESSOR ACOUSTIC SOUND BLANKET
Each compressor is individually enclosed by an
acoustic sound blanket. The sound blankets are made
with one layer of acoustical absorbent textile ber of
15mm (5/8") thickness; one layer of anti-vibrating
heavy material thickness of 3 mm (1/8"). Both are
closed by two sheets of welded PVC, reinforced for
temperature and UV resistance. (Factory-mounted)
ULTRA QUIET FANS
Lower RPM, 8-pole fan motors are used with steeper-
pitch fans. (Factory-mounted)
VIBRATION ISOLATORS
Level adjusting, spring type 25.4mm (1") or seismic
deection or neoprene pad isolators for mounting under
unit base rails. (Field-mounted)