FORM NO.:6U6K-B01E-NB-EN
JOHNSON CONTROLS
130
TABLE 45 – UNIT PARAMETERS
NO.
Short Name
(BACnet Object Name)
Function Code
Register
Address
Note
Unit
1 Software Versions A 3 1000-1009
2 AI1-32 3 1021-1052
3 Chiller EWT 3 1021
4 Ambient Temp 3 1022
5 Ckt1 Coil Temp 3 1023
6 Ckt2 Coil Temp 3 1024
7 Unit LWT 3 1025
8 Chiller LWT 3 1026
9 Ckt1 Suct Temp 3 1027
10 Ckt2 Suct Temp 3 1028
11 Ckt1 Comp1 DLT 3 1029
12 Ckt1 Comp2 DLT 3 1030
13 Ckt2 Comp1 DLT 3 1031
14 Ckt2 Comp2 DLT 3 1032
15 Ckt1 Suct Pr 3 1040
16 Ckt2 Suct Pr 3 1041
17 Ckt1 Disch Pr 3 1042
18 Ckt2 Disch Pr 3 1043
19 3 1054
20
Ckt1 fan motor fault 3 Bit1: 1-Fault
21 Ckt2 fan motor fault 3 Bit2: 1-Fault
22 Ckt1 HPS and Comp1/2 overload 3 Bit3: 1-Fault
23 Ckt1 LPS 3 Bit4: 1-Fault
24 Chiller WFS 3 Bit5: 1-Fault
25 Cooling/Heating mode 3 Bit6: 0-Cooling, 1-Heating
26 Start/Stop mode 3 Bit7: 0-Stop, 1-Start
27 External Interlock 3 Bit8: 1-Fault
28 Power protector 3 Bit9: 1-Fault
29 Ckt2 HPS and Comp1/2 overload 3 Bit10: 1-Fault
30 Ckt2 LPS 3 Bit11: 1-Fault
31 Unit WFS 3 Bit12: 1-Fault
32 3 1055
33 Unit water valve 3 bit0: 1-ON, 0-OFF
34 3 1056
35 Ckt1 fan motor 3 b
it0: 1-ON, 0-OFF
36 Ckt1 fan motor speed 3 bit1: 1-ON, 0-OFF
37 Ckt1 Comp1 3 bit2: 1-ON, 0-OFF
38 Ckt1 Comp2 3 bit3: 1-ON, 0-OFF
39 EVA heater 3 bit4: 1-ON, 1-OFF
40 Ckt1 oil heater 3 bit5: 1-ON, 1-OFF
DI1-16 Status
DO17-32 Status
DO1-16 Status