EasyManua.ls Logo

York YVAA - Table 6 - Standard Two-Pass, Right Side Inlet;Outlet Evaporator Connections (contd)

York YVAA
178 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 5 - TECHNICAL DATA
JOHNSON CONTROLS
71
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
5
TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR (CONT'D)
ALL DIMENSIONS - INCHES (MM)
YVAA
A,B C D
E-NOZZLE
SIZE
WATER
VOLUME.
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
FRAME
COND.
23 3
20.8
(528)
73.2
(1859)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
24 5
21
(533)
92.9
(2360)
56.1
(1425)
8
71
(269)
590
(37)
2190
(138)
24 8
21
(533)
122.9
(3122)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
26 3
21
(533)
117.1
(2974)
56.1
(1425)
8
58
(220)
500
(32)
1970
(124)
27 0
21
(533)
16.8
(427)
51.9
(1318)
8
82
(310)
590
(37)
2190
(138)
27 3
21
(533)
42.9
(1090)
70
(1778)
8
82
(310)
590
(37)
2190
(138)
27 5
22.5
(572)
44.7
(1135)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
27 8
22.5
(572)
88.3
(2243)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
29 5
22.5
(572)
88.6
(2250)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
30 3
21
(533)
122.9
(3122)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permittted. Glycol limits are higher. Please contact your Johnson Controls Sales Ofce for ratings and further information.

Table of Contents

Other manuals for York YVAA