72
SECTION 5 - TECHNICAL DATA
FORM 201.28-NM1.1
ISSUE DATE: 1/31/2018
ALL DIMENSIONS - INCHES (MM)
YVAA
A,B C D
E-NOZZLE
SIZE
WATER
VOLUME.
GALLONS
(LITERS)
MINIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
MAXIMUM
CHILLED
WATER FLOW
RATE
GPM (L/S)
FRAME
COND.
30 5
21
(533)
166.9
(4239)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
30 8
22.5
(572)
132.2
(3358)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
31 8
22.5
(572)
176.6
(4486)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
32 3
22.5
(572)
88.6
(2250)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
33 3
21
(533)
166.9
(4239)
70
(1778)
8
71
(269)
590
(37)
2190
(138)
34 3
22.5
(572)
132.6
(3368)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
34 5
22.5
(572)
176.21
(4476)
71.8
(1824)
10
113
(428)
810
(51)
3200
(202)
36 8
23.3
(592)
208.6
(5298)
83.5
(2121)
10
147
(556)
1090
(69)
3420
(215)
37 3
22.3
(566)
180.9
(4595)
112.2
(2850)
10
96
(363)
840
(53)
3320
(209)
37 5
23.3
(592)
164.3
(4173)
83.4
(2118)
10
147
(556)
1090
(69)
3420
(215)
TABLE 7 - OPTIONAL ONE-PASS EVAPORATOR (CONT'D)
NOTE: Minimum Chilled Water Flow Rate is for full load selections; Variable Primary Flow ratings as low as 50% of the minimum are
permitted. Glycol limits are higher. Please contact your Johnson Controls Sales Ofce for ratings and further information.