EasyManua.ls Logo

York YZF024THRU 060*C - Page 20

York YZF024THRU 060*C
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
20 Johnson Controls Unitary Products
632151-YTG-A-1010
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZF06013(C)
INDOOR COIL MODEL NO. AHX60
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1055 1255 1455
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57
65
T.C. 45.5 49.4 49.3 54.2 59.0 48.2 51.4 51.2 56.0 61.0 50.9 53.3 53.0 57.9 63.0
S.C. 42.4 37.6 32.7 32.6 27.5 44.9 40.8 35.0 34.9 28.8 47.4 44.1 37.4 37.1 30.0
K.W. 1.57 1.57 1.57 1.57 1.56 1.62 1.62 1.62 1.62 1.61 1.67 1.67 1.67 1.67 1.66
75
T.C. 43.8 47.1 47.0 51.7 56.4 46.3 48.8 48.6 53.4 58.3 48.8 50.4 50.2 55.0 60.1
S.C. 40.8 36.7 31.7 31.6 26.4 43.1 39.9 34.0 33.8 27.7 45.5 43.1 36.4 36.0 28.9
K.W. 1.80 1.80 1.80 1.80 1.80 1.85 1.85 1.85 1.85 1.85 1.90 1.90 1.90 1.90 1.90
85
T.C. 42.1 44.8 44.7 49.3 53.8 44.4 46.2 46.1 50.7 55.5 46.8 47.5 47.5 52.1 57.2
S.C. 39.2 35.8 30.7 30.5 25.3 41.4 39.0 33.0 32.7 26.6 43.6 42.2 35.3 35.0 27.8
K.W. 2.03 2.03 2.03 2.03 2.04 2.08 2.08 2.08 2.09 2.09 2.13 2.13 2.13 2.14 2.14
95
T.C. 40.4 42.4 42.5 46.8 51.2 42.5 43.6 43.6 48.0 52.7 44.7 44.7 44.7 49.2 54.3
S.C. 37.6 34.9 29.7 29.5 24.2 39.6 38.0 32.0 31.7 25.5 41.7 41.2 34.3 33.9 26.8
K.W. 2.26 2.26 2.26 2.27 2.27 2.31 2.31 2.31 2.32 2.33 2.37 2.37 2.37 2.37 2.38
105
T.C. 38.2 39.4 39.4 43.5 47.7 40.1 40.7 40.4 44.5 48.9 42.0 41.9 41.3 45.6 50.2
S.C. 35.6 33.7 28.5 28.2 22.7 37.4 36.3 30.7 30.4 24.0 39.2 38.9 33.0 32.6 25.3
K.W. 2.56 2.56 2.56 2.56 2.57 2.61 2.61 2.61 2.62 2.62 2.66 2.66 2.66 2.67 2.68
115
T.C. 36.1 36.4 36.4 40.2 44.1 37.7 37.8 37.1 41.1 45.1 39.3 39.2 37.8 41.9 46.1
S.C. 33.6 32.5 27.2 27.0 21.3 35.1 34.5 29.5 29.1 22.6 36.7 36.5 31.7 31.3 23.8
K.W. 2.86 2.87 2.87 2.86 2.86 2.91 2.91 2.91 2.91 2.92 2.96 2.96 2.96 2.97 2.97
125
T.C. 33.9 33.3 33.4 36.9 40.6 35.3 34.9 33.9 37.6 41.3 36.7 36.5 34.4 38.3 41.9
S.C. 31.6 31.3 26.0 25.7 19.9 32.9 32.8 28.2 27.9 21.1 34.2 34.2 30.4 30.1 22.4
K.W. 3.16 3.17 3.17 3.15 3.16 3.21 3.22 3.21 3.21 3.21 3.26 3.26 3.26 3.26 3.27
NOTE:
ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
MV20D FC/MC62D 0.98 0.96 1.02
MV20D FC64D 0.99 0.99 1.00
Furnace Coil
T.C. S.C. KW
T*(8,L)X*C16 FC/MC62D 0.98 0.95 1.03
T*9X*C16 FC/MC62D 0.99 0.95 1.04
T*9X*C20 FC/MC62D 1.00 0.99 1.01
T*9X*D20 FC/MC62D 1.00 0.99 1.01
(Y*(8,L)C/T*8V)*C16 FC/MC62D 0.98 0.95 1.03
(Y*(8,L)C/T*8V)*C20 FC/MC62D 0.99 0.95 1.04
(Y*9C/T*9V)*C16 FC/MC62D 0.99 0.94 1.05
(Y*9C/T*9V)*C20 FC/MC62D 0.99 0.94 1.05
(Y*9C/T*9V)*D20 FC/MC62D 0.99 0.94 1.05
T*(8,L)X*C16 FC64D 1.00 0.98 1.02
T*(8,L)X*C20 FC64D 0.96 0.89 1.09
T*9X*C16 FC64D 1.00 0.98 1.02
T*9X*C20 FC64D 1.00 1.01 0.99
T*9X*D20 FC64D 1.00 1.02 0.98
(Y*(8,L)C/T*8V)*C16 FC64D 1.00 0.98 1.02
(Y*(8,L)C/T*8V)*C20 FC64D 1.00 0.98 1.02
(Y*9C/T*9V)*C16 FC64D 1.00 0.97 1.03
(Y*9C/T*9V)*C20 FC64D 1.00 0.97 1.03
(Y*9C/T*9V)*D20 FC64D 1.00 0.97 1.03

Related product manuals