632151-YTG-A-1010
Multipliers for determining the performance with other indoor section.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO. YZF04213(C)
INDOOR COIL MODEL NO. AHX60
AIR TEMP.
ENTERING
OUTDOOR
UNIT
AIR TEMP.
ENTERING
INDOOR
COIL
ID CFM
1200 1400 1600
MBTUH KW C.O.P. MBTUH KW C.O.P. MBTUH KW C.O.P.
60
60 46.5 4.55 2.5 47.8 4.72 2.5 49.2 4.89 2.4
70 44.5 4.01 2.8 45.8 4.16 2.7 47.0 4.31 2.6
80 42.5 3.54 3.1 43.7 3.68 3.0 44.9 3.82 2.9
47
60 39.6 3.34 3.0 40.5 3.73 2.7 41.3 4.19 2.3
70 38.2 3.24 3.0 39.0 3.46 2.8 39.8 3.71 2.6
80 36.7 3.14 3.0 37.5 3.22 2.9 38.3 3.30 2.8
40
60 36.1 3.68 2.4 37.0 3.77 2.4 37.8 3.86 2.3
70 34.3 3.22 2.7 35.3 3.31 2.6 36.3 3.41 2.5
80 32.6 2.82 2.9 33.6 2.92 2.9 34.7 3.03 2.8
30
60 28.0 2.98 2.3 30.1 3.16 2.3 32.3 3.33 2.2
70 28.3 2.73 2.6 29.6 2.83 2.5 30.9 2.93 2.5
80 28.5 2.52 2.9 29.0 2.56 2.8 29.5 2.60 2.7
17
60 27.4 2.91 2.3 26.7 2.82 2.3 26.1 2.73 2.2
70 21.4 2.15 2.5 20.9 2.09 2.4 20.4 2.02 2.4
80 15.5 1.48 2.6 15.2 1.43 2.6 14.8 1.38 2.5
10
60 23.7 2.55 2.3 23.8 2.53 2.2 23.8 2.52 2.2
70 18.3 1.86 2.4 18.3 1.85 2.4 18.4 1.83 2.4
80 12.8 1.24 2.6 12.9 1.23 2.5 13.0 1.22 2.5
NOTE:
ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil
MBH KW COP
F6FP060 – 1.01 0.99 1.02
MV20D FC/MC62D 1.01 0.99 1.01
Furnace Coil
MBH KW COP
T*(8,L)X*C16 FC/MC62D 1.00 0.99 1.01
T*(8,L)X*C20 FC/MC62D 1.01 1.01 1.00
T*9X*C16 FC/MC62D 1.01 0.99 1.02
T*9X*C20 FC/MC62D 1.01 1.01 1.00
T*9X*D20 FC/MC62D 1.01 1.01 1.00
(Y*(8,L)C/T*8V)*C16 FC/MC62D 1.01 0.98 1.03
(Y*(8,L)C/T*8V)*C20 FC/MC62D 1.01 0.98 1.03
(Y*9C/T*9V)*D20 FC/MC62D 1.01 0.98 1.03