The value of FILt will determine the ability of filtering noise.
When a large value is set, the measurement input is stabilized but the response
speed is slow. Generally, it can be set to 1 to 3.
If great interference exists, then you can increase parameter “FILt” gradually to make
momentary fluctuation of measured value less than 2 to 5.
When the instrument is being metrological verified, “FILt” s can be set to 0 or 1 to
shorten the response time.
Selection of
power
frequency and
temperature
scale
50C: 50Hz,display ℃. , 50F: 50Hz, display ℉
60C: 60Hz,display ℃. , 60F: 60Hz, display ℉.
Input has max. anti-interference ability to 50Hz or 60Hz frequency when parameter
set;
SSr: Output SSr drive voltage or thyristor zero crossing trigger signal. G, K1 or K3
module should be installed. The output power can be adjusted by the on-off time
proportion. The period (CtI) is generally 0.5~4 seconds.
rELy: for relay contact output or for execution system with mechanical contact switch.
To protect the mechanical switch, the output period (CtI) is limited to 3~120 seconds,
and generally is 1/5 to 1/10 of derivative time.
0-20: 0~20mA linear current output. X3 or X5 module should be installed in OUTP
SSr
r E L y
0-20
4-20
PHA