40
G=0, When the thermocouple or RTD input is burnt out, PV value will increase and
trigger the high limit alarm.
G=1, When the thermocouple or RTD input is burnt out, PV value will increase and
NOT trigger the high limit alarm. After it was sets, High Limit alarm will have 30 sec.
delay for trigger in normal usage.
H=0, AIBUS communication
H=1, MODBUS communication.
Note: AF=0 is recommended.
P A S d
Password
When PASd=0255 or AF.D=0, set Loc=808 can enter the whole parameter table.
When PASd=256 9999 and AF.D=1, only Loc=PASd can access the whole
parameter table.
Please setting PASd cautiously, if the password is lost, you can’t access the
parameter table again.
09999
SPL
Low limit of SV
Minimum value that SV is allowed to be.
-999
+3000
unit
SPH
Upper limit of
SV
Maximum value that SV is allowed to be.
SP1
Setpoint 1
When Pno=0 or 1, then SV=SP1
SPL