9
2.3 UNIT PHYSICAL DATA
MODEL NUMBER MAC240
NOMINAL CAPACITY (TONS) @ 95
0
F AMBIENT 24
CAPACITY (TONS) @ 115
0
F AMBIENT 21
APPLICATION INDUSTRIAL, 100% FRESH AIR
POWER SUPPLY (V-PH-HZ) 460-3-60
COMPRESSOR Type SCROLL
Part # (Qty.) 800-674-19 (2)
Refrigerant R-22
Operating charge per system, oz 450
RLA/LRA, Amps 19.6/125
CONDENSER FAN & MOTOR Type PROPELLER
Part # (Qty.) 800-226-01 (2)
Nominal CFM 15000
Dia. (mm) 700
POWER SUPPLY (V-PH-HZ) 460-3-60
Motor kW - RPM - FLA - LRA 1.5 - 1000- 2.6- 10
EXHAUST FAN Size (mm) 700
Part # (Qty.) 800-237-03 (1)
kW - RPM - FLA - LRA 1.5 - 1000- 2.6- 17.4
MINIMUM CIRCUIT AMPACITY Amps 74
MAX. FUSE SIZE/CIRCUIT BREAKER
Amps 90
UNIT KVA Amps 54.6
CONDENSER COIL Type Inner grooved tubes and enhanced fins
Tube Dia.- Rows - Fins per inch 3/8-5-14
Total face area (Sq. ft.) 25
EVAPORATOR BLOWER Type BACKWARD CURVED
Size (inch) DP/500
Drive type DIRECT DRIVE
Nominal CFM 2400
EVAPORATOR BLOWER MOTOR
Motor KW 13.2
FLA/LRA 21 /111
Motor frame IEC
EVAPORATOR COIL Type CORRUGATED FIN & TUBE
Tube Dia.- Rows - Fins per inch 1/2-12-10
Total face area (Sq. ft.) 6
HIGH PRESSURE SETTING OPEN - PSIG 450 ± 10
CLOSE - PSIG 360 ± 15
LOW PRESSURE SETTING OPEN - PSIG 25 ± 5
CLOSE - PSIG 50 ± 5
AIR COOLED DIESEL ENGINE GENERATOR / WESTAC ( DEUTZ) WPDZ72/F6L914 (85KVA / 68KW )
UNIT DIMENSIONS TRAILER MOUNTED - L x B x H (meters) 3.6 x 2.2 x 2.6
UNIT WEIGHT ( WITHOUT FUEL), KG 4000
TRAILER SPEED LIMIT 15 KM / H