EasyManua.ls Logo

ZIEHL-ABEGG MODBUS RTU System - 3.2 MODBUS Structuring; 4.2 Cable Length Considerations

ZIEHL-ABEGG MODBUS RTU System
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Picture 3: General two-wire topology
In addition to the two signal wires, the MODBUS line can have two other wires for the 24V supply. This
voltage is always required to supply the terminals of the "AXG" type series. The voltage can be fed in
by the rst slave for example.
Attention
Wrong polarity of the supply voltage or switching of the bus wires with the supply voltage wires can
destroy the interfaces. If an RS232/RS485 converter (gateway) is used, this must be electrically
isolated.
3.2 MODBUS structuring
The following pictures show examples of an unsegmented (picture 4) and a segmented (picture 5) bus
structure.
Master
RT + Fail Safe
integrated
Bus 1
1 2 3 62
63
RT
150
Picture 4: One segment with MODBUS master
Bus 1
1
2
63
1 2 63
Bus 1: RT deactivated
Bus 2: RT activated
Bus 2
RT
150
Active
Repeater
RT
150
Master
RT + Fail Safe
integrated
Picture 5: Two segments connected to a repeater
Technical information MODBUS RTU System model series Hardware installation (Bus topology)
R-TIL08_01-GB 1215 Part.-No.
5/16

Related product manuals