15807042 v1.02 08.22 HydroTap G5 UltraCare Install Instructions
Vent tray
The supplied vent tray must be fitted. It provides a safe exhaust for
refrigerant gas in the unlikely event of a leak.
Vent tray dimensions WxDxH (mm): 500 x (515-555) x 40
Refer to the instructions provided with the Vent Tray.
Cold air is drawn in through the inlet vent and gap provided by the door
buffers.
Inlet vent is mounted over cupboard side, door or floor cut-out.
Warm air is exhausted through vent tray.
Observe 100mm inlet / outlet vent separation.
Air outlet
100mm
4mm door buffers
(supplied)
Air inlet options
Vent tray exhaust cut-out
450
40
SECTION 7: Set up the ventilation
Absolute min. vent tray depth 490mm (limit of travel, may affect airflow).