2.1 I Selecng the locaon
• The lter must be installed:
- aer the circulaon pump (see image ),
- before the heang and/or water treatment system (see image ),
- ideally 0.5 metres below the water level (see image : ),
- ideally less than 5 metres from the pool (see image : ),
- in a dry venlated equipment room protected against frost.
• The lter must not be installed:
- in an area subject to ooding, splashing, rain or exposed to direct sunlight,
- more than 1.5 metres above the water level (see image : ),
- near a heat source or source of ammable gas,
- in an equipment room where chemicals are stored, since the emanaons could damage the lter.
• Easy access is required for maintenance work (cover, hydraulic connecon, valves, draining).
• The hydraulic circuit before the lter must be as short as possible to prevent air pockets from becoming lodged in the
pipes, and with the fewest obstacles possible (bends, other appliances), to avoid head loss.
• Place on a stable, level and solid surface (e.g. concrete oor).
• Secure the lter to the ground using stainless steel screws (not included).
• Check that the lter is installed more than 1.5 metres from the pool switch box (see image : ) in order to be able
to stay clear when turning on.
• We strongly recommend ng a check valve if the lter is installed above the water level.
• Installaon of valves upstream and downstream from the lter is mandatory if it is installed below the water level.
: Pump
: Filter
: Heang system
: Water treatment system
: Sucon valves (sucon outlets valves,
skimmers, sucon ports)
: Discharge valve to the pool
: Drainage valve to the drainage system
: Filter
: Pool water Level
: Ideal distance from the lter relave to
the water level (0.5 m)
: Maximum distance above the water level
(1.5 M)
: Ideal distance from the pool
(between 0.4 and 5 m)
: Minimum compulsory distance between
the lter and any switch box (1.5 m)