EasyManua.ls Logo

Zonex DigiTract 4-2 - SYSTEM CONTROLLER - HEAT PUMP DTHP4-2 COMPONENTS

Default Icon
28 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
A. Heat Pump Unit/LAS Terminals Connects to Heat Pump and
Leaving Air Sensor (LAS).
±: LAS terminals. The LAS monitors the heat pump coil leaving air
temperature.
W2: Auxiliary Heat. When energized (W2 made to R), turns on the
heat pump auxiliary heat.
G: Blower. When energized (G made to R), turns on the
indoor blower.
Y1: Compressor. When energized (Y1 made to R), turns on the heat
pump first stage compressor.
Y2: Compressor. When energized, (Y2 made to R), turns on the
heat pump second stage compressor.
O/B: Reversing Valve. When energized (O/B made to R), engages
the heat pump reversing valve.
R: Heat pump unit 24V power. Powers Digitract 4-2 and
thermostats.
E: Emergency Heat. Separate output (E made to R) to cycle additional
stages (if applicable) when in the emergency heat mode.
L: Compressor Fail Flag. Connected to L of STAT1 terminal. See B.
C: Heat pump unit 24V power return.
B. Thermostat Terminals Connects up to four zone heat pump
thermostats.
L: Compressor Fail Flag. On STAT1 only. Connected to L of Heat
Pump Unit terminal (see A). If the heat pump compressor fails,
the heat pump will energize L (R made to L) which will turn on
an indicator light on thermostat 1. This feature is not available
on all heat pumps and/or thermostats.
E: Auxiliary/Emergency Heat. On STAT 1 only. Connected to E
terminal on STAT 1. When thermostat 1 is in the emergency
heat mode and making a heat call, Y is locked out and W is
energized as the first stage of heat. The W2 and E outputs from
the controller will be energized simultaneously.
NOTE: When the controller receives a STAT 1 E input from the
thermostat W terminal when in the normal heat mode, it is
ignored. The W2 output of the controller is cycled according to
leaving air temperature.
0/B: Mode control. For O thermostats, thermostat is in cool mode
when energized (O/B made to R) and in heat mode when not
energized. The reverse is true for B thermostats.
R: Heat pump unit 24V power. See A.
Y: Compressor. When energized (Y made to R), requests that the
DGHP4-2 energize the heat pump compressor.
G: Blower. When energized (G made to R), requests that the
DTHP4-2 energize the indoor blower fan.
C: Heat pump unit 24V power return.
C. Damper Terminals Connects dampers for up to four zones and
damper power supply.
TR1/
TR2: 24V AC transformer terminals. This transformer powers only
the zone dampers.
1 1: Zone damper 1. When energized, powers zone damper 1 closed.
2 2: Zone damper 2. When energized, powers zone damper 2 closed.
3 3: Zone damper 3. When energized, powers zone damper 3 closed.
4 4: Zone damper 4. When energized, powers zone damper 4 closed.
D. Damper Status Lights Light on when corresponding zone
damper is closed.
E. Reversing Valve Selection Jumper Configures Digitract 4-2 to
energize reversing valve in cool mode or heat mode. Place on O and
center pin to energize reversing valve in cool mode. Place on B and
center pin to energize in heat mode.
F. Board Number This number indicates the circuit board number
and revision. May need to know this number if conferring with
technical support.
G. Microcontroller Responsible for activation and control of the
unit and dampers based upon thermostat input. Occasionally
software upgrades may become available. If so, the Digitract 4-2
software can be field upgraded by changing this microcontroller.
H. Power Switch When OFF, power from the heat pump transformer
is disconnected from the Digitract 4-2 and thermostats. When ON, power
from the heat pump transformer is supplied to the Digitract 4-2 and
the zone thermostats.
I. Heat Pump Status LEDs Indicates what the DTHP4-2 is
energizing on the heat pump.
O/B: Reversing valve, yellow. On when the reversing valve is
energized.
Y1: Compressor, yellow. On when the first stage compressor is
energized.
Y2: Compressor, yellow. On when the second stage compressor is
energized.
G: Blower, green. On when the indoor blower is energized.
W2: Auxiliary heat, red. On when the auxiliary heat is energized.
PWR: Power, orange. On when power at R and C and the Power
Switch is on. Flashing when in Capacity Control cut out mode.
See Status Lights section, page 9, for further information.
J. Leaving Air Sensor Potentiometer Turn to calibrate the leaving
air sensor, if required. See Calibration, in Capacity Controller section.
SYSTEM CONTROLLER – HEAT PUMP DTHP4-2
COMPONENTS (Continued)

Related product manuals