ZXMSG 5200 (V2.0) Technical Manual 
26  Confidential and Proprietary Information of ZTE CORPORATION 
Rack Parameters 
The  ZXMSG 5200 can be installed  in an  indoor  or outdoor type rack.  The 
indoor  model  is  ZXA10-ONUB-IN/1500.  The  outdoor  model  is  ZXONU-
OUT30 or ZXONU-OUT40.  
  The working parameters for the ZXA10-ONUB-IN/1500 are as follows:  
DC voltage: -57 V DC ~ -40 V DC 
AC power supply: 200 V AC ~ 240 V AC 
Power consumption (full load): About 700 W 
Working humidity: 20% ~ 80% 
Working temperature: 0ºC ~ +40ºC 
Waterproof  and  dustproof  requirements:  IP  5.5  level  of  the 
International Electrotechnical Commission (IEC). 
Internal battery: Four pieces of 12 V 100 Ah batteries  
Rack weight: About 210 kg (without batteries)  
  The working parameters for the ZXONU-OUT30 are as follows:  
AC power supply: 200 V AC ~ 240 V AC 
DC voltage: -56 V DC ~ -40 V DC 
Power  consumption:  350  W  (maximum  equipment  power  in  the 
cabinet) + 1500 W (power of air conditioners). 
Working temperature: -35ºC ~ +55ºC 
Relative humidity: 5% ~ 90% 
Temperature control solution: To use industrial air conditioner 
Waterproof  and  dustproof  requirements:  IP  5.5  level  of  the 
International Electrotechnical Commission (IEC). 
Internal battery: Four pieces of 12V 100 Ah batteries  
Rack weight: About 320kg (without batteries and air conditioner)  
  The working parameters for the ZXONU-OUT40 are as follows:  
AC power supply: 200 V AC ~ 240 V AC 
DC voltage: -56 V DC ~ -40 V DC 
Power  consumption:  430  W  (maximum  equipment  power  in  the 
cabinet) + 1500 W (power of air conditioners). 
Working  temperature:  The  normal  working  temperature  should  be 
within -35ºC ~ +50ºC (with the consideration of sunny radiation).  
No  more  than  4  hours’  operation  under  the  maximum  temperature 
+55ºC.  
Relative humidity: 5% ~ 90% 
Temperature control solution: To  use industrial air conditioner or heat 
exchanger