EasyManuals Logo

A.O. Smith BTR120 User Manual

A.O. Smith BTR120
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
12
MODEL BTR(C)-250, 251
Input: 250,000, 251,000 Total Vent Height (Feet)
Draft Hood: 6” 6 8 10 15 20 30 50 100
Input Btuh Rise Vent Connector Diameter (in inches)
250/251,000 1 Ft. - - - - - - 8 8
250/251,000 - - - 8 8 8 8 8
250/251,000 3 Ft. - 8 8 8 - 8 7 7
Number Combined Input
of Heaters in Thousands of Btuh Manifold and Common Vent Diameter (In inches)
2 480 14 12 12 10 10 10 8 8
500/502 14 12 12 10 10 10 10 8
3 720 14 14 14 12 12 12 10 10
750/753 16 14 14 14 12 12 10 10
4 960/1000/1004 18 16 16 14 14 14 12 12
MODEL BTR(C)-275
Input: 275,000 Btuh Total Vent Height (Feet)
Draft Hood: 6” 6 8 10 15 20 30 50 100
Input Btuh Rise Vent Connector Diameter (in inches)
275,000 2 Ft. - - - - - 8 8 8
275,000 3 Ft. - - - 8 8 8 8 8
Numbers Combined Input
of Heaters in Thousands of Btuh Manifold and Common Vent Diameter (in inches)
2 550 - - - 1210101010
3 825 - - - 1414121212
4 1100 - - - 1614141212
MODEL BTR(C)-305
Input: 305,000 Btuh Total Vent Height (Feet)
Draft Hood: 8” 6 8 10 15 20 30 50 100
Input Btuh Rise Vent Connector Diameter (in inches)
315,000 1 Ft. - - 10 10 10 10 10 10
305,000 2 Ft. 10 10 10 10 10 10 8 8
365,000 3 Ft. 10 10 10 10 10 8 8 8
Number of Combined Input
Heaters in Thousands of Btuh Manifold & Common Vent Diameter
2 610 14 14 12 12 12 10 10 10
3 915 16 16 16 14 14 12 12 12
4 1220 18 18 16 16 16 14 14 12
MODEL BTR(C)-365, 400
Input: 365,000, 399,000 Total Vent Height (Feet)
Draft Hood: 8” 6 8 10 15 20 30 50 100
Input Btuh Rise Vent Connector Diameter (in inches)
365,000 1 Ft. - - - - - 10 10 10
400,000 - - - - - - 10 10
365,000 2 FT. 12 12 10 10 10 10 10 10
400,000 12 12 12 12 10 10 10 10
365,000 3 FT. 10 10 10 10 10 10 10 10
400,000 12 10 10 10 10 10 10 10
Number of Combined Input
Heaters in Thousands of Btuh Manifold & Common Vent Diameter (inches)
2 730 14 14 14 12 12 12 10 10
800 16 14 14 14 12 12 10 10
3 1095 18 18 16 16 14 14 12 12
1200 18 18 18 16 16 14 14 12
4 1460 20 20 18 18 16 16 14 12
1600 22 20 20 18 18 16 14 14
MODEL BTR(C)-500
Input: 500,000 Btuh Total Vent Height (Feet)
Draft Hood: 8” 6 8 10 15 20 30 50 100
Input Btuh Rise Vent Connector Diameter (in inches)
500,000 2 Ft. - 12 12 12 12 12 12 12
500,000 4 Ft. 12 12 12 12 12 12 10 10
500,000 6 Ft. N/A 12 12 12 12 12 10 10
Number of Combined Input
Heaters in Thousands of Btuh Manifold & Common Vent Diameter (inches)
2 1000 18 16 16 14 14 14 12 12
3 1500 22 20 20 18 16 16 14 12
4 2000 24 22 22 20 20 18 16 14
TECHNICAL DATA VENTING, TABLE 3 (Continued)

Table of Contents