Important. This ATEX Category depends on the 
application (see below) and also on the intrinsic safety 
level of the transmitter supply (associated apparatus) 
which can sometimes suitably be [ib] instead of [ia]. As it 
is well known, the level of an intrinsic safety system is 
determined by the lowest level of the various apparatus 
used, i.e., in the case of [ib] supply, the system takes over 
this level of protection.
— 
— 
— 
— 
Note: the transmitter can be connected to either [ib] or [ia] 
supply (associated apparatus)certified [Ex ia]
Note for “Primary transducer”: see the certification for 
exceptions
Application with Gas Application with Dust
Note: the protection is mainly assured by the “IP” degree 
associated to the low power from supply. This can either be 
[ia] or [ib]
Zone “0” 
Zone “1”
Dangerous 
medium 
(process) 
Tank
Zone “0” / Zone “1” sep-
aration element
Primary transducer
266 Tx
Category 1/2 Ga Ex ia 
Zone “20”
Zone “21”
Dangerous 
medium 
(process) 
Silo
266 Tx
Category 1/2 Da Ex ia
 
 
— T4: Temperature class of the transmitter 
— T5: Temperature class of the transmitter 
— T6: Temperature class of the transmitter 
that provides inside separation elements to seal off the 
shown on the relevant part of the sketches.