EasyManua.ls Logo

ABB 3AXD50000035158 - Pt100 Relays; GM International D1073 S Relay (Programmable); Layout

ABB 3AXD50000035158
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pt100 relays
The option contains 3, 5, or 8 GM International D1073S relays by default. Other configurations
are available as an order-based engineered option. The maximum number of relays is 8.
PRelectronics 9116B1 relays are available as an order-based engineered option.
The option also contains one, two or three DOLD LG5925.48 extension relays in the Safe
torque off and diagnostic circuits.
GM International D1073S relay (programmable)
Layout
Current output1-2
1: + Output channel 1 for Current Source Mode or
Voltage Source Mode
1)
2: - Output channel 1 for Current Source Mode or
Voltage Source Mode
1)
This output has been pre-wired to terminal block X506.
See chapter Circuit diagrams.
Power supply
3: + 24 V DC
4: - 24 V DC
3-4
Output contacts (Alarm A)5-6
Output contacts (Alarm B)7-8
Measuring circuit
13: Input channel 1 for 3-4 wire RTD, Reference
Junction Compensator Option 91 or potentiometer
1)
14: Input channel 1 for 3-4 wire RTD
15: + Input channel 1 for 4 wire RTD, thermocouple
TC or potentiometer
1)
16: Input channel 1 for 3-4 wire RTD, thermocouple
TC or potentiometer
1)
13-16
Programming channelCONF
Supply voltage present"PWR" LED (green)
Burnout detected"BURN" LED (red)
Alarm A
2)
"A" LED (red)
Alarm B
2)
"B" LED (red)
1)
Voltage Source Mode, Reference Junction Compensator Option 91, potentiometer and thermocouple TC are not used in
the particular application described by this manual.
2)
Note: For SIL applications, alarm contacts must be used in series with equal configuration. Relay contact shown in
de-energized position.
34 ATEX-certified motor thermal protection function with Pt100 relays (+L514+Q971)

Table of Contents