Connections Device description
Emission test
Radiated emissions - enclosure ports (30 Mhz
to 1 GHz), CISPR 16-2-3/ EN 55016-2-3
EN 55022/ CISPR 22 class A
Radiated emissions - enclosure ports (1 to 3
GHz), CISPR 16-2-3/ EN 55016-2-3
EN 55022/ CISPR 22 class A
Immunity test
Electrostatic discharge, IEC 61000-4-2 8 kV air / 6 kV contact (level 3), criterion A
Radiated radio-frequency electromagnetic
field, IEC 61000-4-3
20 V/m (level x), criterion A
Impulse magnetic field, IEC 61000-4-9 100 A/m (level 3), criterion A
4.7 Connections
4.7.1 Ethernet interfaces (Port1 - Port4)
Every Ethernet interface detects automatically whether the connected counterpart works as
transmission or network termination device. This way both normal and crossover cables can
be used (MDI/MDI-X).
The Ethernet interface can operate at transmission rates of 10 or 100 Mbps, depending on the
connected devices in half duplex or full duplex mode. The operation mode is detected and set
automatically by the EDS500 devices. A manual configuration is possible.
Ethernet interfaces (Port1 - Port4)
Electrical specification IEEE 802.3
Protocol Fast Ethernet, Auto negotiation, Auto sense
Data rate 100 Mbps, 10 Mbps or auto
Duplex full duplex, half duplex or auto
Transmission / Network termination MDI, MDI-X or auto
Cable shielded CAT5e cable (or better), maximum
length: 100m
Plug type RJ-45 (8P8C)
Circuit classification TNV-1 (acc. IEC 60950-1)
Galvanic isolation 1.5 kV isolation voltage
Overvoltage protection Shield to earth ±4 kV
Electrical fast transient / Burst, IEC 61000-4-4 4 kV (level 4), criterion A
Surge 1.2/50 µs, IEC 61000-4-5 4 kV (level 4), criterion A
Conducted disturbances, induced by radio-
frequency fields, IEC 61000-4-6
10 V (level 3), criterion A
Conducted, common mode disturbances
in the frequency range 0 Hz to 150 kHz,
IEC 61000-4-16
30 V continuous disturbance/ 300 V short
duration disturbance (level 4), criterion A
Conducted emissions - symetrical network
ports (0.15 MHz to 30 MHz)
EN 55032/ CISPR 32 class B
30 1KGT150966 V0001