Product Guide 1MRS758725
SSC600
Product version: 1.0
40
ABB
29.3 Advanced Feeder Application Package
Advanced Feeder Application Package can be selected with order
code Digit 5, and it can be selected for 5,10,15 or 20 feeders.
The size of the package impacts the number of available function
instances. The content of the package is described in the table
below.
Table 122. Protection
Function Name IEC 61850 Name
Number of Instances
5 Feeders 10 Feeders 15 Feeders 20 Feeders
Admittance based earth-fault protection EFPADM 15 30 45 60
Multi-frequency admittance-based earth-
fault protection
MFADPSDE 15 30 45 60
Wattmetric based earth-fault protection WPWDE 15 30 45 60
Transient / intermittent earth-fault protection INTRPTEF 5 10 15 20
Fault locator SCEFRFLO 5 10 15 20
Directional reactive power under voltage
protection
DQPTUV 5 10 15 20
Low voltage ride through protection LVRTPTUV 15 30 45 60
29.4 Transformer Application Package
Transformer Application Package can be selected with order code
Digit 7, and it can be selected for 2 or 4 feeders. The size of the
package impacts the number of available function instances. The
content of the package is described in the table below.
Table 123. Protection
Function Name IEC 61850 Name
Number of Instances
2 Feeders 4 Feeders
Three-phase thermal overload protection
for power transformers, two time constants
T2PTTR 2 4
Stabilized and instantaneous differential
protection for 2-winding transformers
TR2PTDF 2 4
Numerical stabilized low impedance
restricted earth-fault protection
LREFPNDF 2 4
Table 124. Control
Function Name IEC 61850 Name
Number of Instances
2 Feeders 4 Feeders
Tap changer position indication TPOSYLTC 2 4