Technical specifications
Page 3-10 ABB Control - AC 31
1SBC 260400 R1001-b 06.99
40 series 50series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V a.c.
- Weight 400 g 800 g 400 g 800 g
Power supply
- Power supply voltage:
Nominal value
Admissible range
24 V d.c.
19.2 to 30 V
120 / 230 V a.c.
97.75 to
126.5 V or
195.5 to 253 V
24 V d.c.
19.2 à 30 V
120 / 230 V a.c.
97.75 to
126.5 V or
195.5 to 253 V
- Consumption:
central unit alone typical.
Maximum configuration typical.
120 mA
400 mA
30 mA
100 mA
120 mA
400 mA
30 mA
100 mA
- Polarity reversal protection yes no yes no
- 24 V d.c. isolated power for the
inputs:
Voltage range
Output current
Short circuit protection
no
-
-
-
yes
19.2 to 30 V
400 mA
yes
no
-
-
-
yes
19.2 to 30 V
400 mA
yes
- Dissipation 5 W (6 W for 07 CT 41) 10 W 5 W (6 W for 07 KT 51) 10 W
Incorporated binary inputs
- Number of inputs 8 8 8 8 8 8
- Isolation of inputs / electronic 1500 V a.c. 1500 V a.c. 1500 V a.c. 1500 V a.c. 1500 V a.c. 1500 V a.c.
- Input types PNP and
NPN
PNP and
NPN
PNP and
NPN
PNP and
NPN
PNP and
NPN
PNP and
NPN
- Input voltage:
Nominal value
Signal at 0 (IEC 1131-2)
Signal at 1 (IEC 1131-2)
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
24 V d.c.
0 to + 5 V
+ 15 to + 30 V
- Input current at 24 V d.c.:
Inputs I62.02 to I62.07
Inputs I62.00 and I62.01
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
7 mA
9 mA
- Filtering time:
Standard input
Input with counter configuration
Input with interruption
configuration
5 ms
70 µs
90 µs
5 ms
70 µs
90 µs
5 ms
70 µs
90 µs
5 ms
70 µs
90 µs
5 ms
70 µs
90 µs
5 ms
70 µs
90 µs
- Cable length:
Unshielded (not for the high
speed counter inputs)
Shielded
Non standard inputs
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m
300 m
500 m
50 m