Technical specifications
ABB Control - AC 31 Page 3-11
1SBC 260400 R1001-b 06.99
40 series 50 series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V a.c.
Incorporated outputs
- Number of outputs 6 relays 6 transistors 6 relays 6 relays 6 transistors 6 relays
- Isolation of the inputs / electronic 1500 Vrms
1 min
1500 V a.c. 1500 Vrms
1 min
1500 Vrms
1 min
1500 V a.c. 1500 Vrms
1 min
- Total charging current
under voltage:
direct 24 V d.c.
resistive load / inrush current
L / R = 20 ms
L / R = 30 ms
L / R = 40 ms
L / R = 60 ms
alternate 24 to 230 V a.c.
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
1 A for
O62.00 and
O62.01 and
0.5 A for
other outputs
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
1 A for
O62.00 and
O62.01 and
0.5 A for
other outputs
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
- Total charging current 6 x 2 A 4 x 0.5 A
+ 2 x 1 A
6 x 2 A 6 x 2 A 4 x 0.5 A
+ 2 x 1 A
6 x 2 A
- Output leakage current -
< 200 µA
--
< 200 µA
-
- Output waste voltage - 0.5 V to
500 mA max.
- - 0.5 V to
500 mA max.
-
- Minimum cut-off values 10 mA under
12 V d.c.
12 V 10 mA under
12 V d.c.
10 mA under
12 V d.c.
12V 10 mA under
12 V d.c.
- Breaking capacity under 120 V a.c.
(contact rating code B300) (UL)
2 A2 A2 A2 A
- Breaking capacity under 250 V a.c.
(contact rating code B300) (UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
- Number of common 2 (2+4) 2 (2+4) 2 (2+4) 2 (2+4)
- Switching frequency:
for resistive loads
for inductive loads
for lamps
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz < 1 Hz
< 0.2 Hz
< 0.2 Hz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz < 1 Hz
< 0.2 Hz
< 0.2 Hz
- Number of switches:
for AC-1
for AC-15
1 million
100 000
-
-
1 million
100 000
1 million
100 000
-
-
1 million
100 000
- Short circuit and overload
protection
envisage
externally
yes:
thermic
envisage
externally
envisage
externally
yes:
thermic
envisage
externally
- Surge voltage protection envisage
externally
yes envisage
externally
envisage
externally
yes envisage
externally
- Outputs diagnosis no overload and
short circuit
no no overload and
short circuit
no
- Cable length:
unshielded
shielded
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m