EasyManua.ls Logo

ABB AC 31 - 3.5. Incorporated outputs

ABB AC 31
221 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical specifications
ABB Control - AC 31 Page 3-11
1SBC 260400 R1001-b 06.99
40 series 50 series
07 CR 41
24 V d.c.
07 CT 41
24 V d.c.
07 CR 41
120/230 V a.c.
07 KR 51
24 V d.c.
07 KT 51
24 V d.c.
07 KR 51
120/230 V a.c.
Incorporated outputs
- Number of outputs 6 relays 6 transistors 6 relays 6 relays 6 transistors 6 relays
- Isolation of the inputs / electronic 1500 Vrms
1 min
1500 V a.c. 1500 Vrms
1 min
1500 Vrms
1 min
1500 V a.c. 1500 Vrms
1 min
- Total charging current
under voltage:
direct 24 V d.c.
resistive load / inrush current
L / R = 20 ms
L / R = 30 ms
L / R = 40 ms
L / R = 60 ms
alternate 24 to 230 V a.c.
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
1 A for
O62.00 and
O62.01 and
0.5 A for
other outputs
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
1 A for
O62.00 and
O62.01 and
0.5 A for
other outputs
-
2 A / 5 A
2 A
1 A
0.6 A
0.35 A
2 A AC-1
0.5 A AC-15
- Total charging current 6 x 2 A 4 x 0.5 A
+ 2 x 1 A
6 x 2 A 6 x 2 A 4 x 0.5 A
+ 2 x 1 A
6 x 2 A
- Output leakage current -
< 200 µA
--
< 200 µA
-
- Output waste voltage - 0.5 V to
500 mA max.
- - 0.5 V to
500 mA max.
-
- Minimum cut-off values 10 mA under
12 V d.c.
12 V 10 mA under
12 V d.c.
10 mA under
12 V d.c.
12V 10 mA under
12 V d.c.
- Breaking capacity under 120 V a.c.
(contact rating code B300) (UL)
2 A2 A2 A2 A
- Breaking capacity under 250 V a.c.
(contact rating code B300) (UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
2 A (1.5 A
according
to UL)
- Number of common 2 (2+4) 2 (2+4) 2 (2+4) 2 (2+4)
- Switching frequency:
for resistive loads
for inductive loads
for lamps
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz < 1 Hz
< 0.2 Hz
< 0.2 Hz
< 1 Hz
< 0.2 Hz
< 0.2 Hz
5 kHz < 1 Hz
< 0.2 Hz
< 0.2 Hz
- Number of switches:
for AC-1
for AC-15
1 million
100 000
-
-
1 million
100 000
1 million
100 000
-
-
1 million
100 000
- Short circuit and overload
protection
envisage
externally
yes:
thermic
envisage
externally
envisage
externally
yes:
thermic
envisage
externally
- Surge voltage protection envisage
externally
yes envisage
externally
envisage
externally
yes envisage
externally
- Outputs diagnosis no overload and
short circuit
no no overload and
short circuit
no
- Cable length:
unshielded
shielded
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m
150 m
500 m

Table of Contents

Related product manuals