Controller configuration via terminal program Section 7 Commissioning
104 M&I – AC 900F Controller
In case of an invalid entry, the boot loader repeats this configuration item. When the
entry is correct, the real-time clock is started.
Identification PIN
Select the <P>in menu item in order to define an identification PIN.
Enter a four-digit PIN. Confirm the PIN by entering it once again. The PIN prompt
is deactivated when 0000 is entered.
The PIN-protected menus and functions are listed in section 8 (Security).
Starting the operating system
When the above configuration is completed (or upon expiry of the waiting time),
select the <B>ooting menu item. The boot loader attempts to start an existing
operating system or project configuration, if any, or waits for bootstrapping by the
Engineering Station.
RTC time: 22.07.08, 00:17:02 local
Date and time must be precisely set during first commissioning of the AC 900F.
Change PIN (ESC for no change, 0000 to clear)
Enter new PIN: 1234
Confirm PIN: 1234
PIN changed