22 E-Clipse Bypass Configurations for ACH550 Drives
Installation
Note! The settings for ALL external serial communication between the ACH550 with
E-Clipse Bypass and any Building Automation System are configured using the E-
Clipse Bypass operator panel. DO NOT attempt to configure the external serial
communication connection using the ACH550 operator panel!
The settings for internal communication between the ACH550 and the E-Clipse
Bypass are configured at the factory and require no adjustment.
Note! Both the ACH550 Drive and the E-Clipse Bypass include preset application
macros. The only ACH550 Drive macro that provides the proper configuration
settings by default is the "E-Clipse" macro (9902 = 15). If any other ACH550 drive
macro or any modified setting of the "E-Clipse" macro is used the following ACH550
Drive parameter values must be set and power cycled or the E-Clipse Bypass will
not function properly:
Parameter 9802 must be set to “STD MODBUS”
Parameter 1001 must be set to “Comm”
Parameter 1002 must be set to “Comm”
Parameter 1601 must be set to “Comm”
Parameter 1608 must be set to “Comm”
Parameter 5303 must be set to “76.8 kb/s”
Parameter 5304 must be set to “8 EVEN 1”
Parameter 5305 must be set to “DCU PROFILE”
Parameter 5310 must be set to “103”
Parameter 5311 must be set to “104”
Power must be cycled
Refer to the ACH550-UH Users Manual for programming instructions.
Note! Run motor from drive before attempting bypass operation.
System Check: Motor Disconnected from the ACH550 with E-Clipse Bypass
If you are familiar with the E-Clipse Bypass operation, you may skip the following
section. Otherwise, after performing the system checks and setting the ACH550
Drive Start-up Data parameters, become familiar with the operation of the ACH550
Drive with E-Clipse Bypass without the motor connected as follows:
1. Disconnect and lock out power to the E-Clipse Bypass unit, wait at least five minutes
after disconnecting power.
2. Disconnect the motor from the E-Clipse Bypass unit.
3. Apply power to the E-Clipse Bypass unit by turning on the branch circuit disconnect
device and the bypass disconnect switch or circuit breaker.