44 E-Clipse Bypass Configurations for ACH550 Drives
Overview of Bypass Functionality
Note! The learn mode is terminated by any of the following conditions:
 User clears the learn mode request (Parameter 1628 = NOT SEL)
 The running time in learn mode equals the time set by Parameter 1629
 The user enters drive mode.
At the end of learn mode, the average bypass power is calculated.
From that point on, whenever the system is operated in drive mode, it keeps a
running total of the energy savings.
The energy savings is measured from a certain point in time. This starting point is
triggered by any of the following events:
Learn mode is terminated
Drive parameter 0115 (KWH COUNTER) is reset
Bypass parameter 0114 (KWH SAVED) is reset