60 E-Clipse Bypass Configurations for ACH550 Drives
Parameter Descriptions
Group 16
Code Name Resolution Range Default Description
1626 MODE LOCK 1 0 = NOT SEL
1 = AUTO MODE
2 = LOCAL MODE
NOT SEL
(0)
When Mode Lock is AUTO
MODE, the control panel will not
allow switching to Hand or Off.
When Mode Lock is LOCAL
MODE, the control panel will not
allow switching to Auto.
1627 COST/KWH 0.1 c/kWh 0.0 - 100.00 c/kWh 7.0 c/kWh Cost of energy: cents/kWh
1628 LEARN
MODE
10 = NOT SEL
1 = ENABLED
NOT SEL
(0)
When enabled, bypass learns
average power consumption
while operating in bypass mode
1629 LEARN TIME 0.1 Hr 0.0 - 200.0 Hr 48.0 Hr Time that learn mode will be
active after it is enabled
Group 17
Code Name Resolution Range Default Description
1701 OVERRIDE 2 1 0 = NOT SEL
1 = DI5
2 = COMM
NOT SEL
(0)
Selects source for override 2
command.
1702 RUN EN OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGA
RD
(1)
Acknowledge or disregard run
enable during override 2.
1703 ST EN1 OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGA
RD
(1)
Acknowledge or disregard start
enable 1 during override 2.
1704 ST EN2 OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGA
RD
(1)
Acknowledge or disregard start
enable 2 during override 2.
1706 ST EN4 OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGA
RD
(1)
Acknowledge or disregard start
enable 4 during override 2.
1707 FAULTS OVR 1 0 = ACKNOWLEDGE
1 = DISREGARD
DISREGA
RD
(1)
Acknowledge or disregard
overrideable bypass faults during
override 2.
All faults can be overrode except:
3009, 3021, 3022, 3023, 30234,
3027, 3034, 3101, 3202, 3203,
3204, 3205, 3206

Table of Contents