E-Clipse Bypass Configurations for ACH550 Drives 83
Diagnostics and Troubleshooting
4025 LOCAL DISABLED Alarm is displayed if
MODE LOCK (16.29)
is set to AUTO MODE
and the Hand or Off
key is pressed
4026 AUTO DISABLED This alarm is displayed
if MODE LOCK (1629)
is set to LOCAL MODE
and the Auto key is
pressed.
4027 COMM CONFIG ERR Alarm is displayed if
the drive and bypass
MAC addresses are
equal or invalid.
E-Clipse parameters
5002(BP MAC ID) &
5302 (DV MAC ID) are
set to the same value
Change MAC address
to unique values
4028 FBA PAR CONF Non embedded
fieldbus has detected
an error in Group 51
parameters
Verify Group 51
parameters
4029 DRIVE FAULTED The drive is faulted. Reset drive
Alarm
Code
Alarm Name In Panel Alarm Possible Cause Corrective Action