2-78 ACH550 E-Clipse Bypass User’s Manual
Parameters
Group 53: Drive EFB
Group 53: Drive EFB
Code Name Resolution Range Default Description
5301 DV PROT ID hex 0x0000 - 0xFFFF 0x0000 All of drive's Group 53 must be
replicated on bypass, since drive
is configured for Modbus. All
Group 53 functionality associated
with selection by 98.02 shall be
hosted on bypass controller for
drive. Similar parameters shall
be allocated for bypass.
5302 DV MAC ID 1 0 - 65535 1 Drive station ID (NODE
ADDRESS)
5303 BAUD RATE 0.1 kbit/s 1.2, 2.4, 4.8, 9.6, 19.2,
38.4, 57.6, 76.8
9.6 Defines the communication
speed of the RS485 link in kbits
per second (kb/s).
5304 EFB PARITY 1 0=8 NONE 1,
1=8 NONE 2,
2=8 EVEN 1,
3=8 ODD 1
0 Defines the data length, parity
and stop bits to be used with the
RS485 link communication.
5305 PROFILE 1 0=ABB DRV LIM,
1=DCU PROFILE,
2=ABB DRV FULL
— Selects the communications
profile used by the EFB protocol.
5306 DV OK MSG 1 0 - 65535 0 Contains a count of valid
messages received by the drive.
• During normal operation, this
counter is increasing
constantly.
5307 DV CRC ERR 1 0 - 65535 0 Contains a count of the
messages with a CRC error
received by the drive.
5308 UART
ERROR
1 0 - 65535 0 Contains a count of the
messages with a character error
received by the drive.
5309 DV STATUS 1 0=IDLE,
1=EXECUT INIT,
2=TIME OUT,
3=CONFIG ERR,
4=OFF-LINE,
5=ON-LINE,
6=RESET,
7=LISTEN ONLY
0 Contains the status of the drive
EFB protocol.
5310
...
5318
DV PAR 10
...
DV PAR 18
1 0 - 65535 0
5319
...
5320
DV PAR 19
...
DV PAR 20
hex 0x0000 - 0xFFFF 0x0000