59
R1-
R4
R5
R6-
R9
EN
DA
DE
ES
FI
FR
IT
NL
PL
PT
RU
SV
TR
ZH
V UL
UL/NEC
type
ACH580
-01-
Input
current
UL IEC type
ACH580
-01-
Maximum
current
Voltage
rating
Bussmann
type
UL class
A A V
02A1-4 2.1 15 600 JJS-15 T 02A7-4
03A0-4 3.0 15 600 JJS-15 T 03A4-4
03A5-4 3.5 15 600 JJS-15 T 04A1-4
04A8-4 4.8 15 600 JJS-15 T 05A7-4
07A6-4 7.6 15 600 JJS-15 T 09A5-4
012A-4 12.0 15 600 JJS-15 T 12A7-4
014A-4 14.0 30 600 JJS-30 T 018A-4
023A-4 23.0 30 600 JJS-30 T 026A-4
027A-4 27.0 40 600 JJS-40 T 033A-4
034A-4 34.0 60 600 JJS-60 T 039A-4
044A-4 44.0 60 600 JJS-60 T 046A-4
052A-4 52 80 600 JJS-80 T 062A-4
065A-4 62 90 600 JJS-100 T 073A-4
3AXD00000586715.xls J