58
III gC
IV uR or aR
Type
ACH580
-01-
Min.
short-
circuit
current
1)
Input
current
gG (IEC 60269) North
American
type
ACH580
-01-
I
LD
Nominal
current
I
2
t Voltage
rating
ABB type IEC
60269
size
A A A A
2
s V A
3-phase U
N
= 400 or 480 V (380…415 V or 440…480 V) U
N
= 480 V
02A7-4 32 2.6 4 55 500 OFAF000H4 000 02A1-4 2.1
03A4-4 48 3.3 6 110 500 OFAF000H6 000 03A0-4 3.0
04A1-4 48 4.0 6 110 500 OFAF000H6 000 03A5-4 3.5
05A7-4 80 5.6 10 360 500 OFAF000H10 000 04A8-4 4.8
07A3-4 80 7.2 10 360 500 OFAF000H10 000 - -
09A5-4 128 9.4 16 740 500 OFAF000H16 000 07A6-4 7.6
12A7-4 128 12.6 16 740 500 OFAF000H16 000 012A-4 12.0
018A-4 200 17.0 25 2500 500 OFAF000H25 000 014A-4 14.0
026A-4 256 25.0 32 4000 500 OFAF000H32 000 023A-4 23.0
033A-4 320 32.0 40 7700 500 OFAF000H40 000 027A-4 27.0
039A-4 400 38.0 50 16000 500 OFAF000H50 000 034A-4 34.0
046A-4 500 45.0 63 20100 500 OFAF000H63 000 044A-4 44.0
062A-4 800 62 80 37500 500 OFAF000H80 000 052A-4 52
073A-4 1000 73 100 65000 500 OFAF000H100 000 065A-4 65
3AXD00000586715.xls J
1)
Minimum short-circuit current of the installation
Type
ACH580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR
Nominal
current
I
2
t Voltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 400 or 480 V (380…415 V or 440…480 V)
02A7-4 65 2.6 25 130 690 170M1561 000
03A4-4 65 3.3 25 130 690 170M1561 000
04A1-4 65 4.0 25 130 690 170M1561 000
05A7-4 65 5.6 25 130 690 170M1561 000
07A3-4 65 7.2 25 130 690 170M1561 000
09A5-4 65 9.4 25 130 690 170M1561 000
12A7-4 65 12.6 25 130 690 170M1561 000
018A-4 120 17.0 40 460 690 170M1563 000
026A-4 120 25.0 40 460 690 170M1563 000
033A-4 170 32.0 63 1450 690 170M1565 000
039A-4 170 38.0 63 1450 690 170M1565 000
046A-4 280 45.0 80 2550 690 170M1566 000
062A-4 380 62 100 4650 690 170M1567 000
073A-4 480 73 125 8500 690 170M1568 000
3AXD00000586715.xls J
1)
Minimum short-circuit current of the installation