61
Ratings and fuses
I IEC, U
N
= 400 V
II IEC, U
N
= 400 V
III gC
IV uR or aR
Type
ACH580
-01-
Input
rating
Max.
current
Output ratings Heat
dissipation
Air flow Frame
size
Nominal use
I
1
I
max
I
N
P
N
A A A kW W m
3
/h
3-phase U
N
= 400 V (380…415 V)
088A-4 88 122 88 45 1240 139 R5
106A-4 106 148 106 55 1510 139 R5
3AXD00000586715.xls J
Type
ACH580
-01-
Input
rating
Max.
current
Output ratings Heat
dissipation
Air flow Frame
size
North
American
type
ACH580
-01-
Nominal use
I
1
I
max
I
LD
P
LD
A A A hp W ft
3
/min
3-phase U
N
= 480 V (440…480 V)
088A-4 77 122 77 60 1240 82 R5 -
106A-4 96 148 96 75 1510 82 R5 096A-4
3AXD00000586715.xls J
Type
ACH580
-01-
Min.
short-
circuit
current
1)
Input
current
gG (IEC 60269) North
American
type
ACH580
-01-
I
LD
Nominal
current
I
2
t Voltage
rating
ABB type IEC
60269
size
A A A A
2
s V A
3-phase U
N
= 400 or 480 V (380…415 V or 440…480 V) U
N
= 480 V
088A-4 1000 88 100 65000 500 OFAF000H100 000 - -
106A-4 1300 106 125 103000 500 OFAF00H125 00 096A-4 96
3AXD00000586715.xls J
1)
Minimum short-circuit current of the installation
Type
ACH580
-01-
Min. short-
circuit
current
1)
Input
current
uR or aR
Nominal
current
I
2
t Voltage
rating
Bussmann
type
IEC 60269
size
A A A A
2
s V
3-phase U
N
= 400 or 480 V (380…415 V or 440…480 V)
088A-4 480 88 160 16000 690 170M1569 000
106A-4 700 106 200 15000 690 170M3815 1
3AXD00000586715.xls J
1)
Minimum short-circuit current of the installation