11
gG fuses
Type
ACQ580-01-
Min. short-
circuit
current
1)
Input
current
gG (IEC 60269)
Nominal
current
I
2
t Voltage
rating
ABB type IEC
60269
size
A A A A
2
s V
3-phase U
N
= 230 V
04A7-2 200 4.7 25.0 2500.0 500 OFAF000H25 000
06A7-2 200 6.7 25.0 2500.0 500 OFAF000H25 000
07A6-2 200 7.6 25.0 2500.0 500 OFAF000H25 000
012A-2 200 12.0 25.0 2500.0 500 OFAF000H25 000
018A-2 200 16.9 25.0 2500.0 500 OFAF000H25 000
025A-2 320 24.5 40.0 7700.0 500 OFAF000H40 000
032A-2 320 31.2 40.0 7700.0 500 OFAF000H40 000
047A-2 500 46.7 63.0 20100.0 500 OFAF000H63 000
060A-2 500 60.0 63.0 20100.0 500 OFAF000H63 000
3-phase U
N
= 400 or 480 V
02A7-4 32 2.6 4 55 500 OFAF000H4 000
03A4-4 48 3.3 6 110 500 OFAF000H6 000
04A1-4 48 4.0 6 110 500 OFAF000H6 000
05A7-4 80 5.6 10 360 500 OFAF000H10 000
07A3-4 80 7.2 10 360 500 OFAF000H10 000
09A5-4 128 9.4 16 740 500 OFAF000H16 000
12A7-4 128 12.6 16 740 500 OFAF000H16 000
018A-4 200 17.0 25 2500 500 OFAF000H25 000
026A-4 256 25.0 32 4000 500 OFAF000H32 000
033A-4 320 32.0 40 7700 500 OFAF000H40 000
039A-4 400 38.0 50 16000 500 OFAF000H50 000
046A-4 500 45.0 63 20100 500 OFAF000H63 000
062A-4 800 62 80 37500 500 OFAF000H80 000
073A-4 1000 73 100 65000 500 OFAF000H100 000
3AXD00000586715.xls L
1)
Minimum short-circuit current of the installation