9
Ratings and fuses
IEC ratings at U
N
= 230 V, 400 V and 480 V
U
N
= 230 V
Type
ACQ580
-01-
Input
rating
Output ratings Heat
dissipation
Air flow Frame
size
Max.
current
Nominal use
I
1
I
max
I
N
P
N
A A A kW W m
3
/h
3-phase U
N
= 230 V
04A7-2 4.7 6.3 4.7 0.75 45 43 R1
06A7-2 6.7 8.9 6.7 1.1 55 43 R1
07A6-2 7.6 11.9 7.6 1.5 66 43 R1
012A-2 12.0 19.1 12.0 3.0 106 43 R1
018A-2 16.9 22.0 16.9 4.0 133 43 R1
025A-2 24.5 32.7 24.5 5.5 174 101 R2
032A-2 31.2 43.6 31.2 7.5 228 101 R2
047A-2 46.7 62.4 46.7 11 322 179 R3
060A-2 60 83.2 60.0 15 430 179 R3
3AXD00000586715.xls L
Type
ACQ580-01-
Input ratings Output ratings Frame size
I
1
I
N
P
N
A
A
1)
kW
1-phase U
N
= 230 V
04A7-2 3.3 2.2 0.37 R1
06A7-2 4.6 3.2 0.5 R1
07A6-2 6.3 4.2 0.75 R1
12A0-2 8.9 6.0 1.1 R1
018A-2 11.8 6.8 1.5 R1
025A-2 17.3 9.6 2.2 R2
032A-2 30.4 15.2 4.0 R2
047A-2 42 22 5.5 R3
060A-2 55 28 7.5 R3
3AXD00000586715.xls L
1)
Continuous current, no overloadability